Mitsubishi PLC Sequential Start and Stop Control Example
Component Description
- X0: Emergency stop button
- X1, X2, X3: Thermal relays for three motors
- X4: Start button
- X5: Stop button
- Y1, Y2, Y3: Motor contactors
Sequential Start Process
- When the emergency stop and thermal relays are active, M0 auxiliary relay energizes.
- Pressing X4 (start button) energizes Y1, activating the first motor. It also triggers T1 and T2 timers.
- When T1 timer expires, Y2 energizes, starting the second motor.
- When T2 timer expires, Y3 energizes, starting the third motor.
- At this point, all three motors are running in sequence.
Sequential Stop Process
- Pressing X5 (stop button) energizes M1 auxiliary relay, turning off Y3 and activating T3 and T4 timers.
- When T3 timer expires, Y2 deactivates, stopping the second motor.
- When T4 timer expires, Y1 deactivates, stopping the first motor.
- At this stage, all three motors have stopped in sequence.
Emergency Stop Function
- Pressing X0 (emergency stop button) or triggering any thermal relay (X1, X2, X3) immediately cuts power to all motors.
- This ensures safety and prevents equipment damage.
Potential Issue in the Program
The program may contain a design flaw. Can you identify it? Review the logic carefully to find any inefficiencies or safety risks.