Key Benefits
- Low-Cost, Scalable Options: Event reports, waveform capture, reclosure functionality
- Reduced Troubleshooting & Maintenance Costs: Event reports and waveform capture features streamline diagnostic processes.
- Design Flexibility: User-friendly programming logic for easy customization.
- Asset Monitoring: Monitors breaker health and failure.
- Information Access: Modbus RTU communication for remote monitoring and control.
- Configurable Logic and Parameters: Customizable curves, I/O settings, and LEDs.
- Flash Memory for Field Upgrades: Allows for easy system updates.
- Two Settings Groups: Dual configuration options for different operating scenarios.
- Password Protection: Ensures secure local operation.
- Automatic Fault Information Display: Displays last fault data automatically.
- AC/DC Power Supply: Flexible power options for versatile installations.
- Improved User Interface: Enhanced ease of operation.
- Communication Access: Can be accessed through the front panel or remote communication links.
- EnerVista™ Compatibility: Simplifies system setup and monitoring.
- Isolated Front RS232 Serial Port: Ensures secure and isolated data transmission.
Applications
- Primary Feeder Protection: Ideal for use on distribution networks.
- Backup/Auxiliary Protection: Provides protection for transformers, generators, and motors.
Features
Protection and Control
- Phase and Ground TOC & IOC: Time Overcurrent and Instantaneous Overcurrent protection for both phase and ground faults.
- Thermal Image Protection: Monitors the thermal behavior of the feeder.
- IAC Time-Current Curves: Protection curves tailored to industrial and utility applications.
- Circuit Breaker Control: Includes open and close controls for circuit breakers.
- Four-Shot Autorecloser: Automatically restores the feeder after fault clearing.
- Cold Load Pickup: Helps with re-energization after a feeder has been out of service.
- Configurable Breaker Failure: Offers adjustable settings for breaker failure to open.
- Configurable I/O: Customizable I/O settings for flexible integration into control systems.
Monitoring and Metering
- 32-Event Recorder: Records the latest fault events for analysis.
- Oscillography: Captures analog and digital oscillography for detailed fault analysis.
- KI2 Counter for Breaker Maintenance: Tracks breaker operations for maintenance scheduling.
- Per-Phase Current Metering: Provides individual phase current monitoring.
- Last Five Trips Monitoring: Displays data from the last five trips for troubleshooting.
User Interfaces
- EnerVista™ Software: Industry-leading software for device configuration and monitoring.
- LCD Display: 2×16 character display for real-time data and settings.
- LED Indicators: Six LED indicators, four of which are configurable in function and color.
- Communication Ports: RS232 (front) and RS485 (rear) for local and remote communication.
- Multiple Protocols: ModBus RTU, IEC 60870-5-103 for diverse control system integration.
Technical Specifications
Protection
Phase / Ground Time Overcurrent
- Pickup Level: 0.1 – 2.4 times In (rated current) in steps of 0.01 x In.
- Curve Shapes: IEC (A/B/C), ANSI Inverse, IAC Inverse.
- Timing: Adjustable from 0.00 to 600.00 seconds.
- Accuracy: ±1% at rated current, ±3% in complete range.
Phase / Ground Instantaneous Overcurrent
- Pickup Level: 0.1 to 30 times In, with steps of 0.1 x In.
- Operate Time: 20 to 30 ms for I > 1.5 x Actual Pickup.
- Timing Accuracy: ±3% for I > 1.5 x Actual Pickup.
Thermal Image Element
- Pickup Level: 0.1 to 2.4 times In.
- Timing Accuracy: 5% for operate times greater than 2 seconds.
Communications
- Local Communication: 2×16 LCD Display, 5-button keypad.
- Remote Communication: ModBus RTU, Baud rate: 300 to 19200 bps.
- Ports: RS232 (front), RS485 or IEC 60870-5-103 (rear).
Metering
- Accuracy: ±1% at In, ±3% in the full range.
- Current: Fundamental current measurement for precise monitoring.
Monitoring
- Oscillography: Records 1 x 24 cycles with a sampling rate of 8 samples per power frequency cycle.
- Event Recorder: 32 events with time-tagging to 1 ms.
Inputs and Outputs
AC Current Inputs
- Rated Current: 1A or 5A, depending on the model.
- Relay Burden: < 0.2 VA @ In = 5A secondary.
- Current Withstand: 4 x In continuously, 100 x In for 1 second.
Digital Inputs
- Voltage Level: 300 Vdc max for HI power supply; 75 Vdc max for LO power supply.
- Recognition Time: < 4 ms.
Outputs
- Relay Configuration: 6 Electro-Mechanical Form C.
- Relay Material: Silver alloy suited for inductive loads.
- Contact Ratings: 30 A make and carry, 10 A continuous, breaking 4000 VA.
Power Supply
- Low Range: 24 to 48 Vdc, with a backup time of more than 1 week.
- High Range: 110 to 250 Vdc or 110 to 230 Vac.
Mechanical Characteristics
- Package: 1/4 19” rack, 4 units high.
- Protection: IP52 (according to IEC 529).
Environmental Specifications
- Temperature: Operation: -20ºC to +60ºC; Storage: -40ºC to +80ºC.
- Humidity: Up to 95% without condensation.
- Pollution Degree: 2.
Approvals
- Certifications: Conforms to 89/336/CEE and 73/23/CEE, UL508, ISO9001.
Ordering Information
MIF II-P-I-1-1-E-1-0-HI-0-0 (MIFIIPI11E10HI00)
- Base Unit: MIF
- Application: P (3 Phase + Ground relay)
- Curves: I (IEC Curves)
- Phase Ranges: 1 Phase CT In = 1A (0.1-2.4 A)
- Ground Range: 1 Ground CT = 1 A (0.1-2.4 In)
- Language: E (English)
- Options: 1 (Configurable I/O/LEDs, event recording, oscillography)
- Recloser Option: 0 (Without Recloser)
- Power Supply: HI (110-250 Vdc)
- Protocol: 0 (Standard Model – Modbus RTU)
- Conformal Coating: 0 (Without Harsh Environment Conformal Coating)
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat