Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

Honeywell C200/C300 Series/

51306999-175 | Honeywell 8C-TAIM01 LLMUX IOP Module

Brand: Honeywell
Product Family: Series 8
Model Number: 8C-TAIM01
Type: 8C-TAIM01 | 51306999-175 Honeywell Analog Intput Module
Product Origin: USA
Payment: T/T, Western Union, Credit Card
Price: USD 120
Dimensions: 2.5 D x 4.9 W x 12.1 L inches
Weight: 0.56 kg
Warranty: 12 months

  • Product Details

Function

The 8C-TAIM01 Low Level Analog (Temperature) Input (LLMUX) IOP module handles up to 64 channels for temperature inputs. It uses Honeywell’s PMIO LLMUX FTA, with each FTA supporting 16 channels. You can mix RTD, Thermocouple (TC), and millivolt (mV) inputs based on system needs. This module offers high-precision temperature measurements and integrates easily with Honeywell devices.

Notable Features

  • TC and RTD Operation: Supports thermocouples (TC) and RTDs for flexible temperature sensing.
  • Remote Cold Junction Compensation (CJC): Ensures accurate readings by compensating for temperature changes at connection points.
  • Open Thermocouple Detection (OTD): Provides protection against open thermocouple errors.
  • 1 Second PV Scanning: Scans all temperature inputs every second and includes OTD protection.
  • Temperature Points Expansion: You can add temperature points in increments of 16, allowing system scalability.

Temperature Support

The LLMUX system uses solid-state PMIO LLMUX FTA, supporting both RTD and Thermocouple (TC) inputs. The system collects data from all temperature points every second and includes Open Thermocouple Detection (OTD). If a thermocouple is open, the system sets the process variable (PV) to NaN, preventing control errors.

Sampling and Open Sensor Detection

The module detects open sensors before propagating the PV. With OTD enabled, the PV is sampled, and the system checks for errors in the same measurement window. If an error occurs, the PV is set to NaN, and a soft failure is flagged. This prevents invalid readings from affecting the system. Importantly, OTD processing does not introduce delays in PV sampling or reporting.

Detailed Specifications – Low Level Input Multiplexer

ParameterSpecification
Input/Output Model8C-PAIM01, LLMUX, Coated
8U-PAIM01, LLMUX, Uncoated
IOTA Models8C-TAIM01, Coated
8U-TAIM01, Uncoated
FTA ModelsMC-TAMT04, MC-TAMR04
Input TypeThermocouple and/or RTD
Input Channels64 fully isolated channels, in increments of 16
Input Scan Rate1 second fixed by IOM (up to 64 channels/sec max.)
Input Range (TC only)-20 to +100 millivolts
Normal Mode Input Range-10 to +10 Volts (TC); -1 to +2 Volts @ 100mA (RTD)
Gain Error0.050% full scale (for -20 to +100mV range)
Temperature StabilityTC and mV inputs: ±20 ppm/°C max; RTD inputs: ±20 ppm/°C max
Input Impedance1 MΩ at DC (for TC)
Cold Junction Compensation-20°C to +60°C (±0.5°C typical)
RTD Sensor Excitation Current1 mA
Surge ProtectionEN 61000-4-5 (1kV line-to-line, 2kV line-to-ground) for industrial locations
Max Cable Distance1000 feet (16 gauge wire, two twisted pairs per FTA)
Supported RTD TypesPt100 (DIN 4376, JIS C-1604), Ni120, Cu10
Supported Thermocouple TypesANSI specifications J, K, E, T, B, S, R, and more
Open Thermocouple Detection≤ 1000 Ω = no-trip; ≥ 1500 Ω = guaranteed trip
RTD Max Lead Resistance15 Ω
FTA Dimensions2.5 D x 4.9 W x 12.1 L inches (63.5 D x 124.46 W x 307.34 L mm)