General Overview
- Model Number: CC-TDOD51 (Non-Redundant, 9″)
- Alternate Model Number: CC-TDOD61 (Redundant, 12″)
- Product Name: Digital Output Bussed 24VDC (DO24V) Module
- Manufacturer: Honeywell
Functionality
The CC-TDOD51 Digital Output Bussed 24VDC (DO24V) module is designed to control process equipment, such as solenoid valves and interposing relays, by switching reliable 24V digital output signals.
Notable Features
- Comprehensive Internal Diagnostics: Ensures data integrity.
- Optional Redundancy: Supports non-redundant (CC-TDOD51) and redundant (CC-TDOD61) configurations.
- Electronic Overcurrent Protection: Prevents damage from current surges.
- Configurable Safe-State (FAILOPT): On failure, the output can be set to either hold the last value or switch to a safe value, configurable per channel.
- Output Types: Supports latched, pulsed, or pulse-width modulated output on each channel.
Bussed 24VDC Output Details
The Digital Output Bussed 24VDC module supports both internal and external field power excitation:
- Shared Common Ground: All outputs share a common return.
- Power Source Options: Outputs can be powered either by the system power supply or an external 24V power supply.
- Galvanic Isolation: External power source can provide isolation from the Series C power system.
- IOTA Wiring Option: Determines if outputs reference the Series C system power or an external field power source.
FAILOPT (Safe-State) Configuration
- Per Channel Basis: FAILOPT can be set individually for each channel.
- Options:
- Hold Last Value: Retains the last output value on failure.
- Shed to Safe Value: Switches to a predefined safe value (user-configurable).
Detailed Specifications – SINK TYPE 24V DC
Parameter | Specification |
---|---|
Model | CC-PDOD51 – 24V Digital Output, Field Isolated, Bussed Output, Coated |
IOTA Model | CC-TDOD51 (Non-Redundant), CC-TDOD61 (Redundant) |
Output Channels | 32 |
Output Type | SINK (Open Drain) |
Load Voltage | 15–30 VDC (Maximum) |
Load Current | 0.1 A per channel (Maximum) |
Galvanic Isolation | 1000 VAC RMS (System to Field isolation with user-supplied field power) |
On-State Voltage | 0 VDC (Load current @ 0.1A max) |
Off-State Voltage | Typically 24 V |
Off-State Leakage Current | 100 µA (Maximum) |
Turn-On/Turn-Off Time | 10 ms (Maximum) |
Switchover Gap (Redundancy) | None (0 ms) |