General Specifications
- Design: Modular, with metal rack enclosure, CPU, power supply, and customizable I/O modules.
- Mounting: Surface-mounted using 4 screws; designed to IEC 664 and UL840 standards.
- Rack Sizes: Supports 4, 8, or 12 I/O slots with optional redundant power configurations.
I/O Capacity
- Combined I/O: 1920 total points.
- Analog Inputs/Outputs: 960 AI, 200 AO (expandable to 960 with external power).
- Digital I/O: Configurable up to 1920 combined inputs/outputs.
Power Specifications
- Power Supply Options:
- P01: 90–264 VAC, 47–63 Hz, 130 VA input, 60W output.
- P02: 90–264 VAC, 90 VA input, 28W output.
- P24: 21–29 VDC, 72.5W input, 60W output.
- Fuse: Internal (non-replaceable), external user-installed fuse required.
Communication
- Ethernet:
- 2 x 10/100Base-T ports, RJ-45 connectors.
- Protocols: Modbus/TCP, OPC Server, Peer-to-Peer.
- Max 10 host connections.
- RS-232 and RS-485 Ports:
- RS-232: Modem support for remote access.
- RS-485: Up to 2 ports, supporting Honeywell/Modbus RTU protocols, with baud rates up to 115.2 Kbps.
- Remote I/O Support:
- Ethernet: Direct or via switches (up to 4 remote racks).
- Distance: 100m with Ethernet cable; up to 1500m with fiber optics and switches.
Processing & Performance
- Scan Time:
- Normal: 500 ms.
- Fast: As low as 27 ms (dependent on logic block count).
- Function Blocks:
- Max: 5000 user-configurable.
- Types: PID, Cascade, Duplex, Carbon %, etc.
- Auto-tuning: Accutune III with fuzzy logic for overshoot suppression.
Control Features
- Setpoint Programming:
- Up to 50 segments per profile.
- Programmable events, ramp types, and cycles.
- Schedulers and Sequencers:
- 50 segments/schedule, 64 steps/sequencer.
- Recipes:
- Configurable number of variables and profiles.
Environmental
- Temperature:
- Operation: 0–60°C (32–140°F).
- Storage: -40–70°C (-40–158°F).
- Humidity: Up to 95% non-condensing.
- Vibration: 0 Hz to 250 Hz, up to 1 g acceleration.
Approvals
- Certifications:
- CE, ATEX, ABS Type Approval, UL, CSA, and FM (hazardous locations).
- Hazardous Locations:
- FM Class I, Div. 2; CSA Class I, Div. 2.
Additional Notes
- Modbus Support:
- Master: Up to 32 devices, 1024 parameters/controller.
- Slave: Flexible register allocation.
- Redundancy: Supported for power supplies but not for CPU.
- Memory: Supports extensive signal tags (up to 65,535) and user-defined recipes.