Technical Specifications:
Version and Compliance:
- Version: 2.2
- Issued Date: June 2023
- Revision: K
- Compliance:
- EMC Directive 2004/108/EC
- Low-voltage Directive 2006/95/EC
- Designed according to IEC 60255 series international standards
Technical Specifications:
Energizing Quantities:
- Analog Inputs:
- Rated Frequency: 50/60 Hz with operating range of ±10%
- Rated Current: 1 or 5 A with an operating range of (0 – 100) x Ir
- Rated Voltage: 110 or 220 V with an operating range of 0 – 340 V
- Auxiliary AC and DC Voltage:
- DC Voltage Ranges:
- EL = (24 – 60) V or EL = (90 – 250) V, with a nominal range of EL ± 20%
- DC Voltage Ranges:
Binary Inputs and Outputs:
- Modules:
- BIM (Binary Input Module): 16 inputs
- IOM (Input/Output Module): 8 inputs and 10 + 2 outputs
- Contact Data for Relays:
- Maximum system voltage, minimum load voltage, current-carrying capacity, and breaking capacity are specified for different modules.
Influencing Factors:
- Temperature and Humidity:
- Operating Temperature: +20±5°C, nominal range -25°C to +55°C
- Relative Humidity: 45 – 75% (non-condensing)
- Frequency Influence:
- Varying accuracy requirements based on frequency and harmonic frequencies.
Type Tests According to Standards:
- Electromagnetic Compatibility:
- Tested for various disturbances such as 1 MHz burst disturbance, electrostatic discharge, etc.
- Insulation:
- Meets dielectric test, impulse voltage test, and insulation resistance requirements.
- Environmental Conditions:
- Operating temperature range from -25°C to +55°C (continuous) with specified conditions for humidity, pressure, and altitude.
Functions and Technical Data:
Protection Functions:
- Differential Protection:
- Functions like T2WPDIF/T3WPDIF, HZPDIF, and REFPDIF with specific characteristics (e.g., T2WPDIF/T3WPDIF accuracy ±1.0% of Ir at I ≤ Ir and ±1.0% of I at I > Ir).
- Current Protection:
- Includes instantaneous phase overcurrent protection (PHPIOC) and directional phase overcurrent protection (OC4PTOC) with defined current ranges and time-delay characteristics.
- Voltage Protection:
- Two-step undervoltage protection (UV2PTUV) and two-step overvoltage protection (OV2PTOV) with defined voltage ranges and delay settings.
- Frequency Protection:
- Underfrequency protection (SAPTUF), overfrequency protection (SAPTOF), and rate-of-change of frequency protection (SAPFRC) with accurate frequency measurement and time-delay settings.
Hardware Description:
- Modules:
- NUM (Numeric Processing Module): Handles protection functions and logic.
- PSM (Power Supply Module): Provides internal voltages.
- BIM (Binary Input Module): For binary inputs.
- Case Dimensions and Mounting:
- Size: 6U, 1/2 x 19”
- Mounting Options: 19” rack mounting, flush mounting, and wall mounting
Ordering Information:
- Pre-configured IED:
- The ordering code is composed of parts covering product version, configuration options, software, language, casing, mounting, power supply, HMI, analog system, binary I/O modules, station communication, and time synchronization.
- Accessories:
- Includes test switches, protective covers, key switches, and manuals.