General Information
- Product ID: 3BDZ000398R1
- ABB Type Designation: RLM01
- Catalog Description: RLM01, PROFIBUS Redundancy Link Module for PROFIBUS line redundancy
Technical
- Product Type: Interface
- Protocol Type: Profibus-DP
- Number of Channels: 1
- Communication Speed: N/A kbit/s
Technical Information
The Redundancy Link Module (RLM01) converts a non-redundant PROFIBUS line to two redundant lines or vice versa. Field devices equipped with only a single PROFIBUS DP interface can be integrated into the redundant PROFIBUS network using the RLM01. Acting like an active switch, it converts two redundant lines to one PROFIBUS DP line or vice versa. The RLM01 amplifies signal form and amplitude of the incoming data and monitors activities and error statuses of all three lines.
Dimensions
- Product Net Weight: 0.46 kg
Ordering
- Country of Origin: Malta (MT)
- Customs Tariff Number: 85389091
RLM01 Overview of Technical Data
Serial Interfaces
- Connections: A, B, and M
- Transmission Rate: 9.6 kBit/s to 12 MBit/s
- Type: RS 485
- Connection: 9-pin Sub-D connector
- Electrical Isolation: VDE 0110, functionally isolating
- Test Voltage: 500 Veff
- Device Protection Class: 3
Data Telegram Delay
- A/B → M: 1 Bit times [us] + 0.6 us
- M → A/B: 4 Bit times [us] + 0.6 us
Power Supply
- Operating Voltage: 24 VDC (+20 to +33 V)
- Power Consumption: 150 mA typically at 24 V
- Power Loss: Approx. 3.6 W
- Connection: 8-pin terminal strip
- Wire Cross Section: 0.14 to 1.5 mm²
Ambient Conditions
- Operating Temperature: 0 to 50°C
- Transport/Storage Temperature: -30 to 85°C
- Relative Humidity: Max. 75% non-condensing in operation
Alarm Contact
- Function: Open in case of error
- Switching Voltage: < 60 VDC
- Switching Current: Max. 1A
Design
- Dimensions: 134 x 56 x 70 mm (H x W x D)
- Weight: 330 g
- Protection: IP 20
- Attachment: DIN mounting rail, 35 mm
Certification
- USA: UL
- Canada: CSA
- Europe: CE
- Ships and Maritime Systems: Germanischer Lloyd (Category A, B, C, D) when used with 24 VDC power filter (Surge)
Benefits
- Three PROFIBUS ports
- Transparent for PROFIBUS configuration (no slave address required)
- Supports transmission rates of 9.6 Kbps to 12 Mbps
- Serves up to 31 PROFIBUS clients (with repeaters, the number can extend)
- Errors are signalized via an LED on the front plate and a signaling contact
- Specific messages available at the 8-pin terminal strip for diagnostic purposes
- CE, UL, and CSA certified
- Type Approval Certificate from “Germanischer Lloyd” for use in marine areas
Categories
- Products
- Products › Control Systems › 800xA › Device Management PROFIBUS › 800xA PROFIBUS Device Integration › 800xA 4.1 PROFIBUS Device Integration › Communication Modules
- Products › Control Systems › 800xA › Device Management PROFIBUS › 800xA PROFIBUS Device Integration › 800xA 5.0 PROFIBUS Device Integration › Communication Modules
- Products › Control Systems › 800xA › Device Management PROFIBUS › 800xA PROFIBUS Device Integration › 800xA 5.1 PROFIBUS Device Integration › Communication Modules
- Products › Control Systems › 800xA › I/Os › S900 I/O › Communication Modules
- Parts & Services
- Parts & Services › Control Systems › 800xA › I/Os › S900 I/O › Communication Modules
Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat