Description
The DO821 is an 8 channel 230 V a.c./d.c. relay (NC) output module for the S800 I/O. The maximum output voltage is 250 V a.c. and the maximum continuous output current is 3 A. All outputs are individually isolated. Each output channel consists of optical isolation barrier, output state indication LED, relay driver, relay and EMC protection components. The relay supply voltage supervision, derived from the 24 V distributed on the ModuleBus, gives an error signal if the voltage disappears, and the Warning LED turns on. The error signal can be read via the ModuleBus. This supervision can be enabled/disabled with a parameter.
Features and Benefits
- Features and benefits
- 8 channels for 230 V a.c./d.c. relay Normal Closed (NC) outputs
- 8 isolated channels
- Output status indicators
- OSP sets outputs to predetermined state upon error detection
General Information
- Article Number: 3BSE013250R1
- Type: Digital Output Module
- Signal Specification: 230 V a.c./d.c., (5-250 V a.c./d.c.), 3 A per channel
- Number of Channels: 8
- Relay Type: Normally Closed (NC)
- Redundancy: None
- High Integrity: No
- Intrinsic Safety: No
- Compatibility: Works with various MTU modules including TU811, TU813, TU831, TU836, TU837, and TU851.
- HART: No
- SOE (Sequence of Events): No
Detailed Data
Item | Value |
---|---|
Isolation | Individually isolated, channel-to-channel and to circuit common |
Current Limiting | Can be limited by the MTU |
Maximum Field Cable Length | 600 meters (656 yards) |
Rated Insulation Voltage | 250 V |
Dielectric Test Voltage | 2000 V a.c. |
Power Dissipation | Typ. 2.9 W |
Current Consumption (+5 V ModuleBus) | 60 mA |
Current Consumption (+24 V ModuleBus) | 140 mA |
Current Consumption (+24 V External) | 0 |
Front LEDs | Fault (F), Run (R), Warning (W), Output State (OSP), Channel 1-8 Status |
Relay Power Supervision | 24/12 V Relay Power Converter Monitor |
Status Indication of Supervision | Module Error, Module Warning, Channel Error |
Environment and Certification
- CE Mark: Yes
- Electrical Safety: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
- Hazardous Location: None
- Marine Certification: ABS, BV, DNV, LR
- Operating Temperature: 0 to +55°C (+32 to +131°F), approvals issued for +5 to +55°C
- Storage Temperature: -40 to +70°C (-40 to +158°F)
- Pollution Degree: Degree 2, IEC 60664-1
- Corrosion Protection: ISA-S71.04: G3
- Relative Humidity: 5 to 95%, non-condensing
- Max Ambient Temperature: 55°C (131°F), 40°C (104°F) for vertical mounting in compact MTU
- Protection Class: IP20 (IEC 60529)
- Mechanical Operating Conditions: IEC/EN 61131-2
- EMC Compliance: EN 61000-6-4, EN 61000-6-2
- Overvoltage Categories: IEC/EN 60664-1, EN 50178
- Equipment Class: Class I (earth protected)
- RoHS Compliance: DIRECTIVE/2011/65/EN (EN 50581:2012)
- WEEE Compliance: DIRECTIVE/2012/19/EU
Dimensions
- Width: 45 mm (1.77”)
- Depth: 102 mm (4.01”), 111 mm (4.37”) including connector
- Height: 119 mm (4.7”)
- Weight: 0.23 kg (0.5 lbs)
Mounting and Installation
- Compatibility with MTUs: The DO821 module is compatible with various MTU units, including TU811, TU813, TU831, TU836, TU837, and TU851.
- Keying Code: CA (for proper module insertion).
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat