The IntelliVAC is an efficient and flexible solution designed for controlling medium voltage vacuum contactors used in motor starter and feeder applications. It supports both 400 and 800 Amp contactors and can control both electrically held and mechanically latched contactor types.
IntelliVAC Features
Wide Supply Voltage Range: 110 – 240 V AC (50/60 Hz), 110 – 250 V DC, suitable for multiple applications.
Consistent Performance: Vacuum contactor pick-up time remains consistent at a given supply voltage, ensuring repeatable performance.
Selectable Drop-out Time: Optimizes coordination with upstream power fuses.
Altitude Compensation: Electronic altitude compensation for 400 A contactors; 800 A contactors come with a user-friendly altitude adjustment.
Power Loss Ride-through (TDUV): Allows the vacuum contactor to remain closed during brief power loss (external capacitor may be required depending on the ride-through time).
Anti-kiss and Anti-pumping Protection: Prevents rapid re-closure of the contactor due to faulty control devices.
Delayed Restart: Ensures that the vacuum contactor operates within its rated duty cycle.
Temporary Jog Function: Available for electrically held contactors, allowing motor positioning for process set-up.
IntelliVAC Versions
Series A:
One version for electrically held vacuum contactors (single electrical coil, electronically economized).
Another version for mechanically latched vacuum contactors.
Series B:
A single version that controls both electrically held and mechanically latched vacuum contactors.
Note: A Series B IntelliVAC module can replace a Series A module.
Specifications
Mounting & Connections
Mounting: The IntelliVAC control module is mounted using two screws (as shown in Figure 1.3).
Connection: It interfaces with Bulletin 1502 vacuum contactors using “quick” connectors (module-side and contactor-side). Control power and other connections also use “quick” connectors.
Configuration
Configured via DIP switches located on the enclosure (front side).
Bulletin 1500/1900 controllers are pre-configured for the required application.
Firmware
Stored in flash EEPROM and can be updated in the field using a mini-DIN connector accessible inside the enclosure.
Electrical Ratings
Description | Contactor Ratings (Amps) | Control Voltage | AC Rating | DC Rating |
---|---|---|---|---|
Inrush Current (1/2 cycle) | 400/800 | 120/240 | 25 A peak | 25 A peak |
Idle Current (Max without coil energized) | 400/800 | 120/240 | 125 mA | 35 mA |
Hold Current (Max) | 400/800 | 120/240 | 300 mA | 100 mA |
Close Current (0.2 sec) | 800 | 120/240 | 7.0 A | 3.7 A |
Main Input Current (L1 to L2/N) | 400/800 | 120/240 | 3.6 A | 2.0 A |
Command Inputs:
AC: 100 to 240 V rms
DC: 24 to 250 V
Max On-State Current for Open/Close Command: 9mA AC at 250 V AC, 9mA DC at 250 V DC
Max Off-State Current for Open/Close Command: 400 µA AC at 11 V AC, 400 µA DC at 15 V DC
Status Output Contacts:
AC: 250 V rms, 5 A (resistive load); 2 A (reactive, PF=0.4)
DC: 30 V, 5 A (resistive load); 2 A (reactive, L/R=7 ms)
Standards and Approvals
CE, cULus, CSA, IEC (pending)
Mechanical Ratings
Operating Temperature: 0° to 60°C ambient
Non-Operating Temperature: -40° to 85°C
Altitude: -1000 to 5000 meters
Pollution Level: II (as defined by UL 840 and IEC 60664-1)
Shock: 15 g peak, 11 ms
Vibration: 10 to 57 Hz (0.015-inch displacement peak-to-peak), 57 to 150 Hz (2.5 g acceleration)
Altitude Derating
Altitude | DIP Switch Setting | Max Operating Ambient Temperature |
---|---|---|
-1000 to 0 m | 000 | 60°C |
1 to 1000 m | 001 | 60°C |
1001 to 2000 m | 010 | 58°C |
2001 to 3000 m | 011 | 56°C |
3001 to 4000 m | 100 | 54°C |
4001 to 5000 m | 101 | 52°C |
Receiving and Storage
Receiving: Inspect for damage upon arrival and report any damage immediately.
Storage Requirements:
Store in a clean, dry, dust-free environment.
Temperature: -40°C to 85°C (-40°F to 185°F).
Humidity: Maximum 95% (non-condensing).
Spare Parts
IntelliVAC Series B (electrically held and mechanical latch)
Order Number for Series B IntelliVAC: 1503VC-BMC5
Note: The series letter is printed on the large label on the right-hand side of the enclosure, next to the part number.