General Specifications
- User Memory: 512 KBytes
- Input Voltage Rating (Nominal): 24V DC
- Input Voltage Range: 19.2V to 31.2V DC (includes 5% AC ripple)
- Isolation Voltage: 30V DC (Qualification tested to withstand 850V DC for 60 seconds)
Input Current
- 0.85A maximum at 24V DC
- 1.33A maximum at 19.2V DC
Power Dissipation
- 20.4W maximum at 24V DC
- 25.5W maximum at 19.2V DC
Backplane (FLEXBUS) Current Output
- 653mA maximum at 5.1V DC
Thermal Dissipation
- 87 BTU/hour @ 19.2V DC
Weight
- 0.75 kg (1.66 lbs) (no communication cards installed)
Power Supply
- Recommended Models: 1794-PS3 or 1794-PS13
- For CSA compliance, use a SELV power supply compliant with IEC 61010.1, Annex H.
Power Conductors
- Minimum Temperature Rating: 60°C (140°F)
- Wire Sizes: #22 to #14 AWG (0.324 to 2.08 sq. mm) stranded
- Insulation Thickness: 3/64 inch (1.2mm) maximum
- Length: 10m or less
- Power Connector Torque: 5 to 7 inch-pounds (0.6 to 0.8 Nm)
Battery
- Part Number: 1756-BA1 (AB part number 94194801)
- Battery Type: 0.59g lithium
Cables
- Serial Cables:
- 1761-CBLPM02 to 1761-NET-AIC
- 1761-CBLPA00 to 1761-NET-AIC
- 1756-CP3 directly to controller
- 1747-CP3 directly to controller
- Extended Local I/O Cables:
- 1794-CE1 cable (1 foot)
- 1794-CE3 cable (3 feet)
DIN Rail
- Type: Steel, 35 x 7.55mm
- Part Numbers: A-B part number 199-DR1; 46277-3; EN 50022
Operating Temperature
- Range: 0 to 60°C (32 to 140°F)
- Compliance: IEC 60068-2-1 (Operating Cold), IEC 60068-2-2 (Operating Dry Heat), IEC 60068-2-14 (Operating Thermal Shock)
Storage Temperature
- Range: -40 to 85°C (-40 to 185°F)
- Compliance: IEC 60068-2-1 (Un-packaged Non-operating Cold), IEC 60068-2-2 (Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Un-packaged Non-operating Thermal Shock)
Relative Humidity
- Range: 5 to 95% non-condensing (IEC 60068-2-30)
Vibration and Shock
- Vibration: IEC 60068-2-6 (Operating): 5g @ 10-500Hz
- Shock:
- Operating: IEC 60068-2-27: 30g
- Non-operating: 50g
Emissions and Immunity
- Emissions: CISPR 11 Group 1, Class A (with appropriate enclosure)
- ESD Immunity: IEC 61000-4-2: 6kV contact discharges, 8kV air discharges
- Radiated RF Immunity: IEC 61000-4-3: 10V/m from 30MHz to 2000MHz
- EFT/B Immunity: IEC 61000-4-4: ±4kV on power ports, ±2kV on communications ports
- Surge Transient Immunity: IEC 61000-4-5: ±2kV line-earth (CM) on shielded ports
- Conducted RF Immunity: IEC 61000-4-6: 10Vrms from 150kHz to 80MHz
Enclosure Type Rating
- None (open-style)
Certifications
- UL: UL Listed Industrial Control Equipment
- c-UL-us: UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations
- CSA: CSA Certified Process Control Equipment
- CE: Compliant with EU 89/336/EEC EMC Directive
- C-Tick: Compliant with Australian Radiocommunications Act
- EEx: Compliant with EU 94/9/EEC ATEX Directive
Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat