Description
The 1797-TB3 terminal bases have 36 wiring connections to and from a plug-in module. The use of each terminal depends on the module mounted in the base.
Both terminal bases are equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base is connected to other terminal bases.
Component Identification
1. Female Flexbus Connector
2. Terminal Base Unit
3. Male Flexbus Connector
4. Keyswitch
Set to the position required for the installed module.
5. Mounting Holes
For panel mounting.
6, 7, 8. Input/Output Terminal Strips
Used for connecting input/output wiring, -V, and +V connections.
9. Locking Tab
10. Module Locking Latch
11. Cover Plug for Male Flexbus Connector
12. 96-Pin Female I/O Connector
Specifications – 1797-TB3 and 1797-TB3S Terminal Base Units
Number of Terminals
- 1 row of 16, 2 rows of 18.
1797-TB3 Terminal Screw Torque
- 0.8…1.0 Nm (7…9 lb-in).
1797-TB3S Terminal Type
- Spring-clamp.
- To open, insert a bladed screwdriver (2.54-3.05 mm/0.100-0.120 in.) and lift up.
Terminals Assignments
Specific Terminals
- +34, -35, +50, -51, and 96
Female I/O Connector Pins
- 30…32, 62…64, 94…96, 36, 49
All Other Terminals
- Only for intrinsically safe circuits.
- Ui <10V dc
- Ii <2.5 A
- Ci <1 nF
- Li Negligible
Must Not Be Used for Any Connection
- Ui <30V dc
- Ii <100 mA
- Ci <1 nF
- Li Negligible
Flexbus Connection
- Intrinsically Safe:
- Ui <10V dc
- Ii <400 mA
- Ci <1 nF
- Li Negligible
Isolation Voltage
- Channel-to-channel isolation is determined by the inserted module.
Physical Specifications
Weight
- Approximately 200 g.
Dimensions (With Module Installed in Base)
- Metric: 3.7H x 3.7W x 2.7D mm.
- Imperial: 94H x 94W x 69D in.
Environmental Conditions
Operational Temperature
- -20…70°C (-4…158°F).
Storage Temperature
- -40…85°C (-40…185°F).
Relative Humidity
- 5…95% noncondensing.
Shock
- Operating Tested: 15 g peak acceleration, 11 (±1) ms pulse width.
- Nonoperating Tested: 15 g peak acceleration, 11 (±1) ms pulse width.
Vibration
- Tested: 2 g @ 10…500 Hz per IEC 68-2-6.
Conductors
Wire Size
- 4 mm² (12 gauge) stranded max.
Insulation
- 1.2 mm (3/64 in.) insulation max.
Agency Certification
IECEx
- Ex ia IIC T4 Gb
CENELEC
- II 2G Ex ia IIC Gb T4
UL, C-UL
- Class I, Groups A, B, C, and D; Class II, Groups E, F, and G; Class III Hazardous Locations.
- Class I, Zone 1, AEx ib[ia] IIC T4.
FM
- Intrinsically Safe Class I, Div 1, Groups A, B, C, D, T4.
- Associated Apparatus with intrinsically safe Connection Class I, II, III, Div 1, Groups A–G.
- Intrinsically Safe Class I, Zone 1, AEx ib[ia] IIC T4.
INMETRO
- BR-Ex ia IIC T4
Certificates
- IECEx BVS 08.0006X
- CENELEC DMT 98 ATEX E012 U
- UL, C-UL UL File Number E197983
- FM Certificate Number 3009806
- INMETRO 05/UL-BRAE-0019U
Note: Termination connections are unique with each I/O module. Refer to the appropriate I/O module’s installation instructions.
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat