Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

Bently Nevada 3500 System/

Bently Nevada 133819-01 3500/60 RTD/TC Non-Isolated I/O Module Internal Terminations

Brand: Bently Nevada
Product Family: 3500/60
Model Number: 133819-01
Type: RTD/TC Non-Isolated I/O Module
Product Origin: United States
Payment: T/T, Western Union, Credit Card
Price: USD 120
Dimensions: 2.6cm*11.2cm*24.2cm
Weight: 0.4kg
Warranty: 12 months

  • Product Details

The Bently Nevada 133819-01 is an RTD/TC Non-Isolated I/O Module designed for use with the 3500/60 & /61 Temperature Monitors. It provides six channels of temperature monitoring and accepts both Resistance Temperature Detector (RTD) and Thermocouple (TC) temperature inputs.

Specifications


Inputs

  • Signal:
    Accepts 1 to 6 RTD or TC transducer signals.
  • Input Impedance:
    Greater than 10 MΩ for each lead input.
  • Power Consumption:
    3500/60: Nominal consumption of 7 watts.

Transducers

Thermocouples (TCs)
  • Type E: -100°C to +1000°C (-148°F to +1832°F)
  • Type J: 0°C to +760°C (+32°F to +1400°F)
  • Type K: 0°C to +1370°C (+32°F to +2498°F)
  • Type T: -160°C to +400°C (-256°F to +752°F)
Resistance Temperature Detectors (RTDs)
  • 100Ω 3-wire & 4-wire Platinum RTD (alpha = 0.00385):
    • -200°C to +850°C (-328°F to +1562°F)
    • With external barriers: -50°C to +850°C (-122°F to +1562°F)
  • 100Ω 3-wire & 4-wire Platinum RTD (alpha = 0.00392):
    • -200°C to +700°C (-328°F to +1292°F)
    • With external barriers: -50°C to +850°C (-122°F to +1562°F)
  • 120Ω 3-wire & 4-wire Nickel RTD:
    • -80°C to +260°C (-112°F to +500°F)
  • 10Ω 3-wire & 4-wire Copper RTD:
    • -100°C to +260°C (-148°F to +500°F)
    • With external barriers: -50°C to +850°C (-122°F to +1562°F)

Note: Platinum RTDs with 0.00385 alpha are the worldwide industrial standard and are recommended for all applications.
Lower OK limit with external barriers is -50°C.


I/O Modules

  • Isolated TC I/O modules:
    250 Vdc of isolation between channels.

Outputs

  • Front Panel LEDs:
    • OK LED: Indicates when the Temperature Monitor is operating properly.
    • TX/RX LED: Indicates when the Temperature Monitor is communicating with other modules in the 3500 rack.
    • Bypass LED: Indicates when the Temperature Monitor is in Bypass Mode.
  • RTD Current Source Value:
    • 925 ±15 µA @ 25°C per transducer (single supply for the 4-wire RTD and two supplies for the 3-wire).
  • Recorder:
    • +4 to +20 mA: Values are proportional to monitor full-scale. Individual recorder values are provided for each channel. Monitor operation is unaffected by short circuits on recorder outputs.
  • Voltage Compliance (current output):
    • 0 to +12 Vdc range across load. Load resistance is 0 to 600 Ω.
  • Resolution:
    • 0.3662 µA per bit ±0.15% error at room temperature
    • ±0.4% error over temperature range.

Signal Conditioning

  • Accuracy:
    • Internal Termination (Non-Isolated): ±3°C at 25°C (±5.4°F at 77°F).

Contact Us

Let us help you find the automation parts you need with reliable quality and dedicated support!