Description
The 3500/64M Dynamic Pressure Monitor is a single-slot, four-channel device designed to monitor high-temperature pressure transducers. It drives alarms based on dynamic pressure measurements, providing critical machinery protection and operational insights.
This monitor accepts inputs from up to four pressure transducers, measuring bandpass dynamic pressure for each channel. Using the 3500 Rack Configuration Software, you can configure the bandpass corner frequencies and set additional notch filters. The monitor also includes a recorder output for use with control systems.
The main functions of the 3500/64M include:
Machinery protection: Continuously compares monitored parameters against set alarm thresholds to trigger alerts.
Machine status monitoring: Provides essential operational and maintenance information for personnel.
Each channel conditions its input signal to generate measured variables, and you can configure alert and danger setpoints for each variable.
Specifications
Inputs
Accepts from 1 to 4 pressure transducer signals
Input Impedance:
3-wire transducer: 10 kΩ
2-wire transducer: 1.5 MΩ to 3.5 MΩ (typical)
Sensitivity: 100 mV/psi (1.45 mV/mBar)
Outputs
Front Panel LEDs:
OK LED: Indicates proper operation
TX/RX LED: Indicates communication status with other modules
Bypass LED: Indicates when in Bypass Mode
Buffered Transducer Outputs:
One coaxial connector per channel
Short-circuit protection for each connector
Output Impedance: 550 Ω
Transducer Supplies:
3-wire: -24 Vdc
2-wire: 3.3 mA current source @ 22 Vdc (nominal)
Recorder Outputs:
Range: +4 to +20 mA, proportional to full-scale
Monitor unaffected by short circuits
Voltage Compliance (current output): 0 to +12 Vdc across load, with load resistance from 0 to 600 Ω
Resolution: 0.3662 µA per bit
Error: ±0.25% at room temperature; -0.66% to +0.70% over temperature range
Update rate: ~100 ms
Signal Conditioning
Dynamic Pressure
Low Mode: 5 Hz to 4 KHz (extends to 5.285 KHz without LP filter)
High Mode: 10 Hz to 14.75 KHz
Filter Quality:
Low Mode: 10-pole high-pass and low-pass filters
High Mode: 6-pole filters
Cascade Mode: Allows channel 1 input to drive all four channels, enabling separate filter options for each channel.
Line Rejection Filter
Two settings: 50 or 60 Hz
Filter response:
-35 dB (1.8%) of Full Scale within ±0.5 Hz of center frequency
Measured Variables
Dynamic Pressure (direct): The primary measurement for each channel
Physical Dimensions
Height x Width x Depth: 241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in)
Weight: 0.82 kg (1.8 lb)
Alarms
Setpoints: Configurable via 3500 Rack Configuration Software, adjustable from 0 to 100% of full-scale
Accuracy of Setpoints: Within 0.13% of the desired value
Alarm Delays: Programmable from 1 to 60 seconds for alert and danger levels
Alert: 1 to 60 seconds
Danger: 0.1 seconds or from 1 to 60 seconds in 0.1 second intervals
Ordering Information
Part Number
176449-05: 3500/64M Dynamic Pressure Monitor
WeChat
Scan the QR Code with wechat