Description
The Bently Nevada 3300/20-13-02-01-00-00 3300/20 Dual Thrust Position Monitor provides early detection of thrust bearing failure. It continuously measures and monitors two independent shaft axial position channels relative to the machine’s axial clearances. Ideally, axial probes are installed to directly monitor the thrust collar, ensuring accurate position measurement relative to the thrust bearing clearance.
Specifications
Inputs
- Signal: Accepts one or two proximity probe signal inputs
- Input Impedance: 10 kΩ
- Sensitivity: User-programmable:
- 200 mV/mil (8 V/mm)
- 100 mV/mil (4 V/mm)
- Power Consumption: 1.5 W nominal
Signal Conditioning
- Accuracy:
- Typical: ±0.33% of full-scale
- Maximum: ±1% (at +25°C / +77°F)
Outputs
- Recorder Outputs:
- +4 to +20 mA
- 0 to -10 Vdc
- +1 to +5 Vdc
- User-programmable:
- Independent recorder outputs per channel
- Short-circuit protection on recorder outputs
- Recorder Accuracy (at +25°C / +77°F):
- +4 to +20 mA: ±0.7% of signal, ±0.09 mA offset
- +1 to +5 Vdc: ±1.1% of signal, ±10 mV offset
- 0 to -10 Vdc: ±1.1% of signal, ±15 mV offset
- Output Impedance: 100 Ω (Voltage outputs)
- Voltage Compliance (Current outputs): 0 to +12 Vdc across load
- Load resistance: 0 to 600 Ω (for +4 to +20 mA option)
- Buffered Transducer Outputs:
- One coaxial connector per channel (front panel)
- One terminal connection per channel (rear panel)
- Short-circuit protected
- Output Impedance: 100 Ω
- Transducer Supply Voltage: User-programmable:
- -24 Vdc
- -18 Vdc
- Current-limited per monitor circuit board
Note: Contact your sales representative for compatibility with 3000 series transducers in monitoring systems using 3300/7200 series transducers.
Alarms
- Alarm Setpoints:
- Alert and Danger alarms are bi-directional (normal and counter)
- Digital adjustment from 0% to 100% of full-scale
- LCD resolution: ±1.6%
- Alarm repeatability: ±0.39% of full-scale
Displays
- Meter:
- Vertical bargraph LCD display (non-multiplexing)
- 63-segment LCD per channel
- Probe Gap displayed on center scale
- LCD also displays error codes and monitor ADJUST mode
- Resolution: ±1.6% of full-scale
- Size: 83 mm (3.25 inches) (vertical)
LED Indicators
- OK LED (Green):
- ON: System OK (monitor, transducers, field wiring)
- OFF: NOT OK or Channel Bypassed (Bypass LED ON)
- Flashing (5 Hz): Error code stored in memory
- Alarm LED (Red):
- Indicates Alert and Danger status per channel
- Flashing: First Out alarm (independent for Alert and Danger)
- Bypass LED (Red):
- Indicates Danger Bypass and Rack/Channel Bypass per channel
Environmental Limits
- Operating Temperature: 0°C to +65°C (+32°F to +150°F)
- Storage Temperature: -40°C to +85°C (-40°F to +185°F)
- Relative Humidity: Up to 95%, non-condensing
CE Mark Directives
- EMC Directive: Certificate of Conformity: 158710
- Low Voltage Directive: Certificate of Conformity: 135300
Hazardous Area Approvals
- CSA/NRTL/C
- Class I, Div 2
- Groups A, B, C, D
- T4 @ Ta = +65°C
- Certification Number: 150368 – 1002151 (LR 26744)
- ATEX
- II 3 G
- EEx nC[L] IIC T4 @ Ta = -20°C to +60°C
- Installation per document: 132577-01
- Certification Number: BN26744C-55A
Physical
- Space Requirements:
- Occupies one rack position (except positions 1 & 2, reserved for Power Supply & System Monitor)
- Weight: 1 kg (2.2 lbs.)
Ordering Information
Dual Thrust Position Monitor
Model Number: 3300/20-AXX-BXX-CXX-DXX-EXX
Part Number: 3300/20-13-02-01-00-00
Option Descriptions
- A: Full-scale Range Option
- 13 → 2.0-0-2.0 mm
- B: Transducer Input Option
- 02 → 7200 11 mm Proximitor System (100 mV/mil) (not 3300XL)
- C: Alarm Relay Option
- 01 → Epoxy-sealed
- D: Agency Approval Option
- 00 → Not required
- E: Safety Barrier Option
- 00 → None
Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat