Overview
The Bently Nevada 3300/45-02-01-03-00 Dual Differential Expansion Monitor provides two channels of continuous differential expansion monitoring, measuring both the magnitude and direction of expansion.
- Four alarm setpoints (two over and two under alarms) can be configured per channel.
- Channel B can be turned off for machines requiring measurement at only one location.
Specifications
Inputs
- Signal: Accepts two proximity probe transducer signals.
- Input Impedance: 10 kΩ.
- Signal Scale Factor: 20 mV/mil (0.787 V/mm) or 10 mV/mil (0.392 V/mm) (jumper-selectable).
- Power Consumption: 1.5 watts nominal.
Signal Conditioning
- Accuracy:
- Typical: ±0.33% of full-scale.
- Maximum: ±1% of full-scale.
- Specified at: Ambient temperature of +25°C (+77°F).
Outputs
Recorder Outputs
- User-programmable for:
- +4 to +20 mA
- 0 to -10 Vdc
- +1 to +5 Vdc
- Voltage or current outputs are proportional to programmed monitor full-scale.
- Individual recorder outputs are provided for each channel.
- Short-circuit protection ensures uninterrupted monitor operation.
Recorder Accuracy (at +25°C / +77°F)
- +4 to +20 mA: ±0.7% of signal, ±0.09 mA offset.
- +1 to +5 Vdc: ±1.1% of signal, ±10 mV offset.
- 0 to -10 Vdc: ±1.1% of signal, ±15 mV offset.
Output Impedance
- Voltage Outputs: 100 Ω (minimum load resistance: 10 kΩ).
- Current Compliance: 0 to +12 Vdc range across load (0 to 600 Ω when using +4 to +20 mA option).
Buffered Transducer Outputs
- One coaxial connector per transducer on the front panel.
- One terminal connection per channel on the rear panel.
- Short-circuit protected.
- Output Impedance: 100 Ω.
Transducer Supply Voltage
- -24 Vdc, current-limited per channel.
Alarms
Alarm Setpoints
- Both Alert and Danger alarms are digitally adjustable from 0 to 100% of full-scale.
- Adjustable within LCD resolution (±1.6%).
- Once set, alarms are repeatable within ±0.4% of full-scale.
Relay Modules
- Location: One relay module can be installed behind each monitor.
- Requirement: At least one alarm relay module must be ordered with each 3300 System.
Display & Indicators
Meter Display
- Type: Non-multiplexing vertical bargraph LCD.
- Segments: 63 individual LCD segments per channel.
- Probe Gap: Displayed on a third, center scale.
- Additional Functions: Displays error codes and monitor ADJUST mode.
- Resolution: ±1.6% of monitor full-scale.
- Size: 83 mm (3.25 inches), vertical dimension.
LED Indicators
-
OK LED:
- Green (constant ON): Indicates monitor, transducer, and wiring are in good condition.
- OFF: Indicates NOT OK condition or Channel Bypassed (red Bypass LED will be ON).
- Flashing at 1 Hz: Transducer was NOT OK but has recovered.
- Flashing at 5 Hz: Error code(s) stored in memory.
-
Alarm LEDs:
- Two red LEDs per channel (independent for Alert and Danger).
- Flashing LED: Indicates First Out condition.
-
Bypass LEDs:
- Two red LEDs show the status of Danger Bypass and Rack/Channel Bypass functions.
Environmental Limits
- Operating Temperature: 0°C to +65°C (+32°F to +150°F).
- Storage Temperature: -40°C to +85°C (-40°F to +185°F).
- Relative Humidity: Up to 95%, non-condensing.
CE Mark Directives
- EMC Directive: Certificate of Conformity: 158710.
- Low Voltage Directive: Certificate of Conformity: 135300.
Hazardous Area Approvals
- CSA/NRTL/C: Class 1, Division 2, Groups A, B, C, D.
- Temperature Rating: T4 @ Ta = 65°C.
Physical Specifications
- Rack Space Requirements:
- First and second slots in the rack are reserved for the Power Supply and System Monitor.
- The monitor can be placed in any other available rack position.
- Rack size depends on the number of monitors used.
- Weight: 1 kg (2.2 lbs.).
Ordering Information
- Type: Dual Differential Expansion Monitor
- Part Number: 3300/45-02-01-03-00
- Ordering Code: 3300/45-AXX-BXX-CXX-DXX
Option Descriptions
A: Full-scale Range Option
- 02: 0 – 10 mm
B: Transducer Input Option
- 01: 25 mm transducer
- Note: 25 mm and 35 mm transducers cannot be used with full-scale range options 05 through 08.
C: Alarm Relay Option
- 03: Quad Relay (Epoxy-sealed only)
Notes:
- At least one relay module must be ordered with each 3300 System.
- If a common relay module is ordered per system, all other monitors of this type will be jumper-programmed at the factory to activate Relay Bus One.
- AND voting logic is not available with Quad Relays.
D: Agency Approval Option
- 00: Not required.