Description
Differential Expansion measures the axial position of the rotor relative to the machine casing at a certain distance from the thrust bearing. Changes in axial position impact axial clearances and are typically caused by thermal expansion during startup and shutdown.
This measurement is usually performed using a proximity probe transducer mounted on the machine casing, observing an axial surface (e.g., collar) of the rotor. It is commonly part of a Turbine Supervisory Instrumentation system.
The 3300/45 Dual Differential Expansion Monitor provides two channels of continuous differential expansion monitoring. It tracks both the magnitude and direction of differential expansion and allows four alarm setpoints (two over and two under alarms) per channel. Channel B can be turned OFF if only one location measurement is required.
Specifications
Inputs
- Signal: Accepts two proximity probe transducer signals
- Input Impedance: 10 kΩ
- Signal Scale Factor: 20 mV/mil (0.787 V/mm) or 10 mV/mil (0.392 V/mm), jumper-selectable
- Power Consumption: Nominal 1.5 watts
Signal Conditioning
- Accuracy: ±0.33% of full-scale (typical), ±1% (maximum) at +25°C (+77°F)
Outputs
Recorder Output
User-programmable options:
- +4 to +20 mA
- 0 to -10 Vdc
- +1 to +5 Vdc
Outputs are proportional to the programmed monitor full-scale. Each channel has individual recorder outputs, and short circuits do not affect monitor operation.
Recorder Accuracy (@ +25°C / +77°F):
- +4 to +20 mA: ±0.7% of signal, 0.09 mA offset
- +1 to +5 Vdc: ±1.1% of signal, 10 mV offset
- 0 to -10 Vdc: ±1.1% of signal, 15 mV offset
Output Impedance:
- Voltage outputs: 100 Ω (minimum load resistance: 10 kΩ)
- Current outputs: 0 to +12 Vdc range across 0-600 Ω load
Buffered Transducer Outputs
- One coaxial connector per transducer (front panel)
- One terminal connection per channel (rear panel)
- Short circuit protected
Transducer Supply Voltage
- -24 Vdc, current-limited per channel
Alarms
- Alarm Setpoints: Adjustable from 0 to 100% of full-scale
- LCD Resolution: ±1.6% of full-scale
- Alarm Repeatability: ±0.4% of full-scale
Relay Modules
- Location: One relay module can be installed behind each monitor
- Requirement: At least one alarm relay module per 3300 System
Display & Indicators
LCD Display
- Type: Non-multiplexing vertical bargraph Liquid Crystal Display (LCD)
- Segments: 63 LCD segments per channel
- Additional Features: Displays probe gap, error codes, and ADJUST mode
- Size: 83 mm (3.25 in) vertical dimension
- Resolution: ±1.6% of monitor full-scale
LED Indicators
-
OK LED (Green):
- Constant ON: Monitor, transducers, and field wiring are OK
- OFF: NOT OK or channel bypassed (Bypass LED ON)
- Flashing at 1 Hz: Transducer was NOT OK but is now OK
- Flashing at 5 Hz: Error code(s) stored in memory
-
Alarm LEDs (Red):
- Two per channel (Alert & Danger)
- Flashing LED: Indicates First Out condition
-
Bypass LEDs (Red):
- Indicate Danger Bypass and Rack/Channel Bypass status
Environmental Limits
- Operating Temperature: 0°C to +65°C (+32°F to +150°F)
- Storage Temperature: -40°C to +85°C (-40°F to +185°F)
- Relative Humidity: Up to 95% non-condensing
Certifications & Compliance
CE Mark Directives
- EMC Directive
- Low Voltage Directive
Certificates of Conformity
- 158710
- 135300
Hazardous Area Approvals
- CSA/NRTL/C Class 1 Division 2, Groups A, B, C, D
- T4 @ Ta = 65°C
Physical Specifications
Rack Space Requirements
- First & second slots in rack reserved for Power Supply and System Monitor
- Monitor can be placed in any available rack position
- Rack size depends on the number of monitors used
Weight
- 1 kg (2.2 lbs.)
Ordering Information
Tachometer Options
Overspeed Protection System Part Number
3300/53-AA-BB-CC-DD-EE-FF-GG-HH
Example: 3300/53-03-02-00-60-05-00-00-00
AA – System Configuration
- 03: 3-Channel System
BB – Power Input Voltage
- 02: 220 Vac power supply
CC – Events Per Revolution (Hundreds)
- 00: 0 Hundreds of events per revolution
DD – Events Per Revolution (Units)
- 60: 60 Units of events per revolution
EE – Recorder Full-Scale Range
- 05: 5000 RPM Recorder Full Scale
FF – Agency Approvals
- 00: No agency approval
GG – Coil 1 Voltage Rating
- 00: Non-BASEEFA Approval
HH – Coil 2 Voltage Rating
- 00: Non-BASEEFA Approval