Description
The 3500/25 Enhanced Keyphasor Module is a half-height, two-channel module designed for use in a 3500 Machinery Protection System. It receives input signals from proximity probes or magnetic pickups, converting them into digital Keyphasor signals. These signals indicate when the Keyphasor mark on a rotating shaft coincides with the Keyphasor transducer, providing crucial rotational speed data. The module can handle up to four Keyphasor signals in a standard configuration or up to eight in a paired configuration.
Specifications
Power Consumption:
- 3.2 Watts (typical)
Signal Inputs:
- The module accepts up to two transducer signals per channel, from proximity probes or magnetic pickups.
- Input range for Non-Isolated I/O modules: +0.8 V to -21.0 V
- Input range for Isolated I/O modules: +5V to -11V
- Passive magnetic pickups require a minimum shaft speed of 200 rpm (3.3 Hz).
Input Impedance:
- 21.8 kΩ (minimum)
Signal Conditioning:
- Speed/Frequency Signal Ranges: 1 to 1,200,000 cpm (0.017 to 20 kHz), supporting multiple events per revolution up to 20 kHz.
- Output range: 1 to 99,999 cpm (0.017 to 1667 Hz)
- Accuracy (at +25°C / +77°F):
- Non-processed signals:
- 0.017 to 100 Hz: ±1 cpm
- 101 to 500 Hz: ±8 cpm
- 501 to 20 kHz: ±1% of cpm
- Processed signals:
- 0.017 to 60 Hz: ±1 cpm
- 61 to 150 Hz: ±8 cpm
- 151 to 20 kHz: ±1% of cpm
- Non-processed signals:
Transducer Conditioning:
- Auto Threshold: Minimum 2 V peak-to-peak amplitude for triggering, with a minimum frequency of 120 rpm (2 Hz).
- Manual Threshold: User-selectable from 0 to -20 V DC, with a minimum signal amplitude of 500 mV peak-to-peak.
- Hysteresis: Adjustable from 0.2 to 2.5 Volts.
Outputs:
- Two buffered Keyphasor outputs at the front via coaxial connectors, and two more outputs at the back via Euro-style connectors.
- Output Impedance: 504 Ω maximum for buffered output.
Keyphasor Transducer Power Supply:
- -24 V DC, 40 mA maximum per channel.
Ordering Information
Model Number: 3500/25-02-01-01 (or variations depending on specifications)
Key Features to Specify:
- A – Number of Channels:
- 0 2: Two half-height 2-channel Keyphasor cards (order for 4 channels).
- B – Type of I/O Module:
- 0 1: I/O module with Internal Terminations.
- C – Agency Approval Option:
- 0 0: Not required.
Spares
- 149369-01: Enhanced Keyphasor Module (can replace 125792-01 Keyphasor Module).
- 125800-01: Keyphasor I/O Module with Internal Terminations.
Ordering Considerations
- External termination blocks cannot be used with internal termination I/O modules.
- When using external terminations, the external blocks and cables must be ordered separately.
- For more advanced signal processing functions, consulting a Bently Nevada sales representative is recommended.
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat