Emerson KC3011X1-BA1 AO Plus, 16-Ch 4-20mA HART
Part Number: ATEX148
Hazardous Atmosphere Classification:
- Ex II 3 G Ex nA IIC Gc
- FM15ATEX0004U
- IECEX FMG 15.0001U
Removal and Insertion:
- Field Power Removal: Power must be removed before disconnecting or connecting the device.
- System Power: Cannot be removed or inserted with system power energized.
Power Specifications:
- Local Bus Power: 12 VDC at 160 mA
- Bussed Field Power: 24 VDC at 400 mA
- Field Circuit: 17 VDC at 23 mA
Environmental Specifications:
- Ambient Temperature: -40 °C to +70 °C
- Shock: 10 g half-sine wave for 11 ms
- Vibration:
- 1 mm peak-to-peak from 2 to 13.2 Hz
- 0.7 g from 13.2 to 150 Hz
- Airborne Contaminants: ISA-S71.04-1985 Class G3
- Relative Humidity: 5 to 95% Non-Condensing
Terminal Block Key Position:
- A5
Maintenance and Adjustment:
- No User-Serviceable Parts: Do not disassemble the unit.
- Calibration: No calibration required.
Other Safety Approvals:
- ES: 1 Div. 2
- FM: CL. 1 Div. 2
- HAZ LOC.: GP A, B, C, D
- ACCESS: TEMP. Rating T4
- CURSE: CL. 1 Div. 2
Warnings:
- Installation, Removal, and Operation: Follow specific instructions for hazardous areas, as outlined in the Delta VTM Scalable Process System Zone 2 Installation Instructions (document 12P2046) and the DeltaVTM S-series and CHARMS Hardware Installation manual.
Additional Information:
- Product Label: Includes serial number, location, and date of manufacture.
- Rotary Keying System: Ensures compatibility between I/O cards and terminal blocks after installation. The terminal block must match the I/O card keying.