The EMERSON EPRO CON021 is an advanced Eddy Current Signal Converter designed for critical applications in turbo machinery. It is used in steam, gas, and hydro turbines, compressors, pumps, and fans to measure radial and axial shaft displacement, position, eccentricity, and speed/key.
Dynamic Performance
Parameter | Specification |
---|---|
Frequency Range (-3 dB) | 0 to 20000 Hz |
Rise Time | <15 µs |
Compatible Models | PR6422, PR6423, PR6424, PR6425, PR6426, PR6453 |
Note: The PR6425 always requires an extended range converter (CON021/91x-xxx).
Environmental Specifications
Parameter | Specification |
---|---|
Operating Temperature Range | -30 to 100°C (-22 to 212°F) |
Shock and Vibration | 5g @ 60 Hz @ 25°C (77°F) |
Protection Class | IP20 |
Power & Electrical Specifications
Parameter | Specification |
---|---|
Supply Voltage Range | -23V to -32V (Output Range: -4V to -20V) -21V to -32V (Output Range: -2V to -18V) |
Connections | Self-locking Lemo-Plug for transducer; Screw Terminal for supply/output (max. 1.5mm² wire) |
Physical Specifications
Parameter | Specification |
---|---|
Housing Material | LMgSi 0.5 F22 |
Weight | ~120 grams (4.24 oz) |
Mounting | 4 Screws M5x20 (included in delivery) |
Compliance and Certifications
CE 2014/30/EU, 2014/34/EU, 2011/65/EU
EN61326-1, DIN EN 50581
ATEX EN 60079-0:2009, EN 60079-11:2012
IEC-Ex IEC 60079-0:2007-10; Edition 5, IEC 60079-11:2011
CSA CAN/CSA-C22.2 NO. 0-M91, CAN/CSA-C22.2 NO. 157-92
UL ANSI/UL Standard 913-2004, ANSI/UL Standard 1604-1995
Hazardous Area Approvals
Intrinsic Safety (iA)
ATEX II 2 G Ex ia IIC T4 Gb (-20°C ≤ Ta ≤ 80°C)
IEC-Ex Ex ia IIC T4 Gb (-20°C ≤ Ta ≤ 80°C)
CSA Class I Division 1, Groups A, B, C, D, T4 (-25°C ≤ Ta ≤ 80°C)
Non-sparking (nA)
CSA Class I Division 2, Groups A, B, C, D
Ex nA II T3..T4, AEx nA II T3..T4 (-25°C ≤ Ta ≤ 80°C)
Ordering Information
Model Number | Sensor Type | Measuring Range | Linearity Error |
---|---|---|---|
CON021 | PR6422 | 1.0mm (Standard Range) | ≤ 1.5% |
CON021 | PR6423 | 2.0mm (Standard Range) | ≤ 1.0% |
CON021 | PR6424 | 4.0mm (Standard Range) | ≤ 1.5% |
CON021 | PR6426 | 8.0mm (Standard Range) | ≤ 1.5% |
CON021/912-015 | PR6422 | 1.5mm (Extended Range) | ≤ 2.0% |
CON021/913-030 | PR6423 | 3.0mm (Extended Range) | ≤ 1.5% |
CON021/913-040 | PR6423 | 4.0mm (Extended Range) | ≤ 2.0% |
CON021/914-060 | PR6424 | 6.0mm (Extended Range) | ≤ 1.0% |
CON021/914-080 | PR6424 | 8.0mm (Extended Range) | ≤ 1.5% |
CON021/914-100 | PR6424 | 10.0mm (Extended Range) | ≤ 2.0% |
CON021/915-040 | PR6425 | 4.0mm (Standard Range) | ≤ 1.5% |
CON021/915-060 | PR6425 | 6.0mm (Extended Range) | ≤ 2.0% |
CON021/915-080 | PR6425 | 8.0mm (Extended Range) | ≤ 3.0% |
CON021/915-100 | PR6425 | 10.0mm (Extended Range) | ≤ 4.0% |
CON021/916-120 | PR6426 | 12.0mm (Extended Range) | ≤ 1.5% |
CON021/916-160 | PR6426 | 16.0mm (Extended Range) | ≤ 2.0% |
CON021/916-200 | PR6426 | 20.0mm (Extended Range) | ≤ 2.5% |
CON021/916-240 | PR6426 | 24.0mm (Extended Range) | ≤ 3.5% |
Dimensions

EMERSON-CON021-Dimensions-1

EMERSON-CON021-Dimensions-2
Here’s a breakdown of the key dimensions from the drawing:
Top View Dimensions:
- Overall Width: 56 mm
- Main Body Width: 50.8 mm
- Distance between Mounting Holes (Horizontal): 50.8 mm
- Distance from Bottom to Center of Mounting Holes: 26 mm
- Distance from Top to Center of Mounting Holes: 11 mm
- Overall Height: 72 mm
- Distance from Bottom to Bottom Mounting Holes: 6 mm
- Mounting Hole Size: 4x 5.3 mm (diameter) and 2x 4.2 mm (diameter)
Bottom View Dimensions:
- Overall Width: 41 mm
Other Notable Features:
- Terminal Connections: The drawing indicates terminals for -24V, 18 (ground), and OUT (output signal).
Important Notes:
- Units: All dimensions are in millimeters (mm).
- Interpretations: The “4x 5.3” and “2x 4.2” likely refer to the number and diameter of mounting holes.
- Context: This drawing provides the physical dimensions necessary for installation and mounting of the CON021 converter.