The EPRO MMS 6822 Interface Card is designed to provide seamless communication between RS 485 devices and MODBUS RTU or TCP/IP networks.
Technical Data:
Data Input:
- Type: 6-fold
- Connection: Via 48-pin measurement connector at the rear.
- Protocol: RS 485 EPRO protocol
- Selectable Baud Rate: 38.4 or 57.6 kBaud
Data Output:
- MODBUS RTU:
- Via 48-pin measurement connector at the rear.
- Selectable Baud Rate: 9.6 or 19.2 kBaud.
- MODBUS via Ethernet TCP/IP:
- Via front-mounted RJ 45 connectors using standard network cables.
- Transmission Standard: Ethernet 10 Base T.
Power Supply:
- Voltage Range: 18…24…31.2 V DC redundant, according to IEC 654-2, Class DC4.
- Power Consumption: Max. 3 W.
Environmental Conditions:
- Protection Class:
- Module: IP00 according to DIN 40050.
- Front Plate: IP21 according to DIN 40050.
- Operating Temperature Range: -10°C to +65°C.
- Storage and Transport Temperature Range: -40°C to +85°C.
- Relative Humidity: 5% to 95%, non-condensing.
Vibration Resistance:
- Standard: According to IEC 68-2, Part 6.
- Vibration Amplitude: 0.15 mm in the range of 10–55 Hz.
- Vibration Acceleration: 16.6 m/s² in the range of 55–150 Hz.
Shock Resistance:
- Standard: According to IEC 68-2, Part 29.
- Peak Acceleration Value: 98 m/s².
- Nominal Shock Duration: 16 ms.
EMC Resistance:
- According to EN50081-1 / EN50082-2.