The HIMA F 7126A Power Supply is designed for H51q systems to provide reliable and safe power conversion between 24 VDC and 5 VDC. It ensures compliance with international standards for electrical safety and EMC, offering robust performance even under challenging industrial conditions.
Key Features
- Voltage Specifications:
- Input: 24 VDC
- Output: 5 VDC
- Supply Voltage Range: 24 VDC (-15% to +20%)
- Transient Voltage Tolerance: Short-term dips up to 20 ms.
- Safety Compliance:
- Supports SELV (Safety Extra Low Voltage) or PELV (Protective Extra Low Voltage) requirements.
- Adheres to NAMUR NE 21 recommendations for handling voltage dips.
- Mechanical Design:
- Compact H41q Devices:
- Subrack: 19-inch technology, 5 HU for central and I/O modules.
- Max. 13 I/O modules (width: 4 SU).
- Modular H51q Devices:
- Central Subrack: 19-inch technology, 5 HU.
- Max. 16 I/O subracks (4 HU each).
- Max. 256 I/O modules (width: 4 SU).
- Modular unit dimensions adhere to 1 SU = 5.08 mm and 1 HU = 44.45 mm.
- Compact H41q Devices:
- Power Distribution:
- Decoupled central unit power supply for voltage dip protection.
- Noise blanking is parameterizable.
- Connection and Wiring:
- Front plate connections with LED displays for digital I/O modules.
- Fire-retardant wires/cables are mandatory.
- RS485 and Ethernet communication interfaces for system programming and expansion.
- Ambient and Operating Conditions:
- Operating Temperature: 0°C to +60°C (per IEC 61131-2).
- Storage Temperature: -40°C to +85°C (without batteries).
- Pollution Degree: II (per DIN VDE 0160).
System Data
Central Module Specifications
- Processor: Intel 386 EX (25 MHz).
- Memory:
- Flash-EPROM for the operating system, function blocks, and user programs.
- CMOS-RAM with lithium battery backup.
- Diagnostics:
- Built-in system diagnostics with alphanumeric display and LEDs.
- Error reporting for central device, I/O bus, and safety modules.
- Cycle Times:
- 5 ms for single-channel systems.
- 27 ms for redundant systems.
Interfaces
- RS485:
- Max. 12 interfaces for H51q systems.
- Baud Rate: 300 bps to 57,600 bps.
- Ethernet:
- IEEE 802.3 with 100BaseT.
- Max. 10 interfaces for redundant H51q configurations.
- Speed: 100 Mbit/s.
- Profibus-DP:
- Max. 10 interfaces for redundant systems.
- Speed: up to 12 Mbit/s.
Signal Definitions (IEC/EN 61131-2)
Input Signals
- L-Signal (0-Signal): -3 to +5 V or open input.
- H-Signal (1-Signal): +13 to +33 V (typical switching point: ~9 V).
Output Signals
- L-Signal (0-Signal): 0 to +2 V.
- H-Signal (1-Signal): +16 to +30 V.
Contact Us
- Phone: +86-15915488782
- Email: uma@meloauto.com
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat