Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

GE Fanuc IC200 / IC300 PLC/

GE VersaMax IC200ALG262 IC200ALG262G Differential Current input Module

Brand: General Electric
Product Family: VersaMax
Model Number: IC200ALG262G / IC200ALG262
Type: Analog Input Module
Product Origin: USA
Payment: T/T, Western Union, Credit Card
Price: USD 120
Dimensions: 2.5 cm x 10.8 cm x 12.7 cm
Weight: 0.1 kg
Warranty: 12 months

  • Product Details

The IC200ALG262 is a differential current input module from the VersaMax I/O platform, designed to interface with analog signal-generating instruments. Manufactured by Emerson Automation, this module is equipped with eight channels to receive standard current input signals (0-20 mA and 4-20 mA).

Key Features:

  • Channels: 8 analog input channels supporting single-ended configurations.
  • Current Ranges: Configurable for 0-20 mA or 4-20 mA using terminal jumpers.
  • Built-in ADC: 15-bit resolution for accurate analog-to-digital conversion.
  • Power Supply: Draws power from the backplane; no external power supply required.
  • Update Rate: 7.5 ms, allowing for real-time monitoring of input signals.
  • Diagnostics: Capable of detecting loss of internal power and open wire faults.

Technical Specifications

Specification Details
Manufacturer GE Fanuc / Emerson Automation
Part Number IC200ALG262 IC200ALG262G
Series VersaMax
Product Type Analog Input Module
Number of Inputs 8
Wiring Configuration Differential
Input Signal, Nominal 0-20 mA; 4-20 mA
Converter Resolution 15 Bits
Update Rate 7.5 milliseconds
Common Mode Range -10 V to +10 V
Input Impedance 100 Ohms
Common Mode Rejection 70 dB
Maximum Current Draw 200 mA from 5 VDC
LED Indicators OK LED (indicates backplane power)

Input Characteristics

  • Input Current Range:
    • Default (no jumper): 4-20 mA
    • With jumper: 0-20 mA
  • Accuracy (0V Common Mode) at 25°C:
    • ±0.3% typical of full scale
    • ±0.5% maximum of full scale
  • Digital Resolution:
    • 0.5 µA = 1 count (for 4-20 mA)
    • 0.625 µA = 1 count (for 0-20 mA)

Diagnostics and Isolation

  • Isolation:
    • Optical isolation between user input and logic.
    • Group to group and channel to channel isolation (250 VAC continuous; 1500 VAC for 1 minute).
  • Diagnostics:
    • Loss of user side power and open wire detection for 4-20 mA signals only.

Installation Notes

  • Connection Recommendations:
    • Use shielded twisted pair cables for analog channel connections. Grounding should occur at the source device or at the I/O module if grounding at the source is not possible.

Additional Information

  • Module IDs:
    • FFFFB508 (4-20 mA range)
    • FFFFFB408 (0-20 mA range)
  • Common Operating Environment:
    • Designed for integration with field transmitters measuring pressure, level, flow, temperature, and more.

Version Information

  • IC200ALG262G: Manufacturing location changed, with no impact on compatibility, functionality, or performance.

Contact Us

Let us help you find the automation parts you need with reliable quality and dedicated support!

Next:

Leave a Reply

Phone +8615915488782

Skype live:.cid.2196513eef2d5350

WhatsApp 8615915488782

WeChat QR Code WeChat

E-Mail uma@meloauto.com

Back to top Back to top

WeChat

WeChat QR Code

Scan the QR Code with WeChat

Leave a message