Product Overview
The HIMA F8650E Central Module is a key component for safety-related systems used in PES (Process Automation Systems), such as H51q-MS, HS, and HRS. It is designed to meet safety requirements for SIL 1 to SIL 3 and AK 1 to AK 6, making it suitable for applications where safety is a critical concern.
Technical Specifications
- Type: F8650E Central Module
- Use: For safety-related systems in PES H51q-MS, HS, HRS
- Safety-Related Requirements: SIL 1 – 3, AK 1 – 6
Processor and Memory
- Microprocessor:
- Intel 386EX, 32-bit
- Clock Frequency: 25 MHz
- Memory per Microprocessor:
- Flash-EPROM: 1 MB
- SRAM: 1 MB (Efficiency dependent on the operating system version)
- Operating System: Custom operating system supporting user programs and data handling
Interfaces and Diagnostics
- Serial Interfaces:
- Two RS-485 interfaces with galvanic insulation.
- Diagnostic Display:
- Four-digit matrix display for error and system diagnostics.
- Two LEDs for error indication (CPU and I/O).
- Toggle switches and push-button for detailed error information and error reset (ACK function).
- Shutdown on Fault: Safety-related watchdog with a 24 VDC output, up to 500 mA current drain, and short-circuit protection.
Physical Characteristics
- Construction:
- Two European standard PCBs: one for the central module and one for the diagnostic display.
- Space Requirements: 8 TE
- Operating Voltage: 5 V, 2 A
- Cooling: If upgrading from an F8650 to the F8650E, modification to the cooling fan concept is required.
Pin Allocation for RS-485 Interface
- Pin 1: Not used
- Pin 2: RP (5V, decoupled by diodes)
- Pin 3: A/A’ (RxD/TxD-A, Receive/Transmit Data A)
- Pin 4: CNTR-A (Control signal A)
- Pin 5: C/C’ (DGND, Data Ground)
- Pin 6: VP (5V, positive pole of power supply)
- Pin 7: Not used
- Pin 8: B/B’ (RxD/TxD-B, Receive/Transmit Data B)
- Pin 9: CNTR-B (Control signal B)
- Switch Settings:
- S1-8: Transmission rate (9600 bps when ON, 57600 bps when OFF)
- S1-1/2/3/4/5: Set the bus station number
Additional Features
- Backup Battery:
- Lifetime of backup battery with mains power off: 100 days at 60°C
- Recommended battery replacement every 2 years (e.g., CR 2477N, HIMA part no. 44 0000018).
- Event Handling:
- Up to 2048 events can be defined
- 500 events can be stored in the event buffer
Notes for Start-up and Maintenance
- Check the bus station number and transmission rate at switch S1 for correct settings.
- Battery: Lifetime of the backup battery is about 100 days when the main power is off at 60°C.