Technical Data
General
- Type Number: 10024/H/F 26800
- Approvals: CE, UL, TÜV
- Software Versions: ≥ 2.78f (configuration ≥ 530)
- Space Requirements: 8 TE, 3 HE (8 HP, 3U)
Communication
- Maximum Baud Rate:
- H-interface (A): 2 Mbaud
- F-interface (B): 38.4 Kbaud
Isolation
- Galvanic Isolation (F-interface only): > 6 kV
Cable Lengths
- H-interface (A): Max. 1.5 m (4.9 ft) at 2 Mbaud (using Belden 9728 or Belden 8314 cable)
- F-interface (B):
- ≤ 19k2: Max. 15 m (49.2 ft)
- 38k4: Max. 10 m (32.8 ft) (if proper cable types are used)
Connectors
- Connector Type:
- H-interface (A): Male, 9 pins
- F-interface (B): Female, 9 pins
Power
- Power Requirements: 5 V DC, 500 mA
- Ripple Content: < 50 mV p-p
Important Note
Do not remove or replace this module while the power to its central part is on.
Contact Us
- Phone: +86-15915488782
- Email: uma@meloauto.com
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat