Parameter Specification
- FTA Models: MU-TDIY22
- No. of Points per IOP/FTA: 32
- Galvanic Isolation (any input terminal voltage referenced to common):
- 30 Vac, ±42.4 Vdc (max)
- Isolation Technique: Optical (in IOP)
- DI Power Voltage Range: 15 to 30 Vdc
- Input Signal Direction: Source/Sink
- ON Sense Voltage/Current:
- 13 Vdc (min) or 3 mA (min)
- OFF Sense Voltage/Current:
- 5 Vdc (max) or 1.2 mA (max)
- Input Impedance: 4.2 KΩ
- Absolute Delay Across Input Filter and Isolation: 5 ms ± 20%
- Field Resistance for Guaranteed ON Condition:
- 300 Ω max @ 15 Vdc
- Field Resistance for Guaranteed OFF Condition:
- 30 KΩ min @ 30 Vdc
- Surge Withstand Capability: ANSI/IEEE C37.90.1-1978