Brand: Honeywell
Product Family: Series 8 I/O
Model Number: 8C-PAIH51
Type: Analog Input Module with HART
Product Origin: USA
Payment: T/T, Western Union, Credit Card
Price: USD 120
Dimensions: 6.1 cm x 15.7 cm x 14.4 cm
Weight: 0.3 kg
Warranty: 12 months

  • Product Details
  • Technical Documentation

The 8C-PAIH51 is an analog input module designed to accept high-level current inputs from transmitters and sensing devices. It is HART-enabled, allowing communication with multivariable instruments for efficient data collection.


Notable Features

  1. Extensive Diagnostics:
    • Built-in self-diagnostics ensure reliable operation and rapid issue detection.
  2. Optional Redundancy:
    • Compatible with redundant IOTA models for enhanced system reliability.
  3. Non-Incendive Field Power:
    • Supplies power directly to the 4-20 mA loop without external marshalling, meeting Division 2 hazardous area requirements.
  4. HART Communication:
    • Supports HART-capable instruments, enabling multivariable data communication and fast collection of control variables.
  5. Fast Loop Scan:
    • Ensures quick updates for real-time monitoring.

Specifications

Model Variants

Model Description
8C-PAIH51 Analog Input with HART, Coated
8U-PAIH51 Analog Input with HART, Uncoated

IOTA Models

Model Description
8C-TAIX51 Non-Redundant, Coated, 6 inches
8U-TAIX51 Non-Redundant, Uncoated, 6 inches
8C-TAIX61 Redundant, Coated, 12 inches
8U-TAIX61 Redundant, Uncoated, 12 inches

Input Characteristics

Parameter Specification
Input Type Current (2-wire or self-powered transmitters)
Input Channels 16 (All single-ended)
Input Range 4-20 mA (via 200 Ω resistor)
A/D Converter Resolution 16 bits
Normal Mode Rejection Ratio 19 dB at 60 Hz
Normal Mode Filter Response Single-pole RC, -3 dB @ 6.5 Hz
Crosstalk -60 dB (dc to 60 Hz)
Maximum Input Voltage ±30 V (no damage)
Input Scan Rate 50 ms
Hardware Accuracy ±0.075% of full-scale (23.5°C ± 2°C)
±0.15% of full-scale (0 to 60°C)

Field Power Conditioning

Feature Description
Protection Individually protected current-limiting circuits
Interfacing Supports Class 1, Division 2 non-incendive devices
Fusing No external fusing required

Contact Us

Let us help you find the automation parts you need with reliable quality and dedicated support!

Prev:

Next:

Leave a Reply

Phone +8615915488782

Skype live:.cid.2196513eef2d5350

WhatsApp 8615915488782

WeChat QR Code WeChat

E-Mail [email protected]

Back to top Back to top

WeChat

WeChat QR Code

Scan the QR Code with WeChat

Leave a message