Overview
The Honeywell 900G01-0102 digital input module supplies 15VDC to external switching hardware, enabling contact closure detection. It features 16 single-ended inputs with galvanic isolation for reliable performance. LED indicators provide real-time status monitoring, and logic control allows state inversion when needed.
General Information
Parameter | Details |
---|
Brand | Honeywell |
Model | 900G01-0102 |
Category | Digital Input Module |
Input Type | Contact Closure |
Inputs per Module | 16 (Single-Ended) |
Electrical Specifications
Parameter | Details |
---|
Voltage Supplied | 15 VDC nominal (provided by controller) |
Maximum Contact Resistance | 1000 ohms |
Switching Current | 2.6 mA nominal |
Galvanic Isolation | Isolation between field wiring and module (microcontroller or backplane) |
Response Time
Parameter | Details |
---|
OFF to ON Response Time | 4 ms max |
ON to OFF Response Time | 6 ms max |
* These values exclude controller scan time and transmission time from module to backplane.
Power Consumption
Parameter | Details |
---|
5V Power Supply Loading | 130 mA max |
24V Power Supply Loading | 40 mA max |
Status Indicators
Indicator Type | Function |
---|
Green LED (Per Channel) | Indicates when a digital input is ON |
Green Blinking LED | Shows that the module is being scanned |
Amber Blinking LED | Highlights forced channels |
Red LED | Signals a module diagnostics error |