The Honeywell CC-PUIO31 Universal Process I/O Module is a versatile and robust module that supports various field device types with notable flexibility and advanced features. Here’s an analysis of its key features and specifications:
Key Functions
- Multi-functionality:
- Each channel can be configured as:
- Analog Input (AI)
- Analog Output (AO)
- Digital Input (DI)
- Digital Output (DO)
- Pulse Input (PI)
- Supports Sequence of Events (SOE) logging with 1ms resolution.
- Each channel can be configured as:
- Protection and Diagnostics:
- Open Wire Detection (OWD)
- Electronic short circuit protection.
- Safe-state (FAILOPT) behavior configuration for outputs.
- HART Communication:
- HART 7 support for both AI and AO.
- Dedicated HART modem per channel for faster performance.
- High Environmental Tolerance:
- Extended operating temperature range: -40°C to +70°C.
Specifications by Function
Analog Input (AI)
- Channels: Up to 32.
- Input Range: 0-20 mA or 4-20 mA.
- Impedance: 250 Ω.
- Accuracy:
- 0.1% FS at 23.5°C.
- 0.25% FS at -40°C to +70°C.
- Scan Rate: 10 ms.
- Features:
- Open Wire Detection.
- Short circuit current limit: 25 mA.
Analog Output (AO)
- Channels: Up to 32.
- Output Range: 4-20 mA.
- Accuracy:
- 0.35% FS at 25°C.
- Includes linearity.
- Resolution: 12-bit.
- Response Time:
- 80 ms in HART mode.
- 0.25 ms in non-HART mode.
- Load: Maximum 825 Ω at 20 mA.
Digital Input (DI)
- Channels: Up to 32.
- Resolution: 1ms (SOE).
- Open/Closed Detection:
- Open: < 2.0 mA.
- Closed: > 3.2 mA.
- Open Wire Detection: Current thresholds configurable.
Digital Output (DO)
- Channels: Up to 32.
- Type: Solid-state source, short circuit protected.
- Load Current:
- On: 1 mA to 0.5 A (per channel).
- Off: < 0.1 mA.
- Voltage: 24 V typical when on.
Pulse Input (PI)
- Channels: Any 4 channels.
- Frequency: 0-15 kHz.
- Minimum Pulse Width: 25 µs.
- Duty Cycle: Configurable.
Unique Features
- HART Support: Enhances diagnostics and communication for AI and AO channels.
- Energy Limitation: Certified for Zone 2/Division 2 hazardous locations.
- Short Circuit Protection:
- Limits current rapidly to protect the module.
- No effect on other channels during short conditions.
- Failover Behavior:
- Configurable safe-state behavior for both AI and AO.
Models and Redundancy
- Non-Redundant: CC-TUIO31 (9” IOTA).
- Redundant: CC-TUIO41 (12” IOTA).
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat