The FC-DCOM-232/485 is a communication FTA (Field Termination Assembly) module designed for use in Safety Manager (SM) systems, enabling both RS-232 and RS-485 communication with various devices, including SM-SM SafeNet and third-party equipment. This module is critical for safe, reliable communication in industrial control and automation systems.
Key Features:
- Dual Communication Interfaces: Supports both RS-232 and RS-485/422 communication, offering versatility in different system setups.
- RS-232 Preference: This FTA is the preferred choice for RS-232 communication, offering compatibility with a wide range of devices.
- Redundant Configuration: The communication FTA can be powered by one or a redundant pair of Control Processors (no separate power supply needed).
- Grounding: The module requires connection to earth ground for proper shielding and safety.
- Flexible Baud Rate Options: The module supports baud rates from 0-250 kBaud for RS-232 and 0-2 MBaud for RS-485/422 (transparent, FM0, FM1, or Manchester coded).
- Mounting: It has a universal snap-in provision for DIN EN rails (TS32 / TS35 × 7.5).
Technical Specifications:
General Information:
- Model Numbers:
- FS-DCOM-232/485
- FC-DCOM-232/485
- Approvals:
- CE, TÜV, UL, FM
Physical Dimensions:
- Module Dimensions:
- 110 × 70 × 61 mm (L × W × H)
- 4.33 × 2.76 × 2.40 in (L × W × H)
- Terminal Dimensions:
- 6 × 57 × 47 mm (L × W × H)
- 0.24 × 2.24 × 1.85 in (L × W × H)
- DIN Rail Compatibility:
- TS32 / TS35 × 7.5
- Used Rail Length: 117 mm (4.6 in)
Power Requirements:
- Input Voltage: 5 V DC ±5%
- Input Current: Max 500 mA, supplied by the connected Control Processor(s).
Communication:
- RS232 Output: According to EIA/TIA-232 standards.
- Baud Rate Range: 0 to 250 kBaud.
- RS485/422 Output: According to EIA/TIA-485-A standards.
- Baud Rate Range: 0 to 2 MBaud (transparent, FM0, FM1, or Manchester coded).
Usage:
- SM-SM SafeNet Communication: Used for communication between Safety Managers and other devices in industrial automation and control environments.
- Not for 1M or 2M Baud Rate: It is not compatible with RS-485 FSC-SM SafeNet communication at 1M or 2M baud rates.
- Preferred for RS-232: This FTA module is ideal for RS-232 communication setups.
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat