Functionality
The TPSU-2430 is a DC/DC converter module that provides an isolated 30 V DC / 1 A output. It powers field termination assemblies (FTAs) such as the TSAI-1620m and TSHART-1620m. Additionally, the module offers voltage monitoring capabilities, including local LED indications and alarm functions via a read-back relay contact.
Key Features
- Voltage Monitoring:
- Local LED indication for output voltage status.
- Read-back relay contact closes when output voltage is within the acceptable range.
- Galvanic Isolation:
- Isolates input, output, and relay contact connections for safety and system integrity.
- Robust Design:
- Short-circuit proof output with overvoltage protection.
- High efficiency (>75%) with natural convection cooling.
- Safety Compliance:
- Certified for SIL3 applications.
- Meets standards such as CE, TUV, UL, CSA, and FM.
- Mounting Options:
- DIN rail mounting (TS32/TS35).
- Can be installed horizontally or vertically.
Connections
Input Terminals
Terminal |
Function |
1 |
Read-back contact |
2 |
Read-back contact |
3 |
24 V DC IN (+) |
4 |
24 V DC IN (–) |
Output Terminals
Terminal |
Function |
1A, 2A, … 6A |
30 V DC OUT |
1B, 2B, … 6B |
0 V DC OUT or Ground1 |
Note: The “0 V DC OUT” must be connected to ground or to a dedicated Earth Leakage Detector (ELD) for predictable system behavior in case of a short to earth.
Specifications
General
Parameter |
Specification |
Type Numbers |
FS-TPSU-2430, FC-TPSU-2430 |
Safety Class |
SIL3 |
MTBF |
Approximately 400,000 hours |
Electrical
Parameter |
Specification |
Input Voltage |
Nominal: 24 V DC; Range: 18–36 V DC |
Inrush Current |
≤ 4 A |
Output Voltage |
30 V DC ± 0.25 V |
Output Current |
1 A (short-circuit proof) |
Ripple (0–30 MHz) |
< 0.1 V RMS |
Short-Circuit Current |
< 3.3 A |
Overvoltage Protection |
33 V |
Efficiency |
> 75% |
Environmental
Parameter |
Specification |
Operating Temperature |
-5°C to +70°C (23°F to 158°F) |
Storage Temperature |
-40°C to +85°C (-40°F to +185°F) |
Altitude |
≤ 2000 m |
Cooling |
Natural convection |
Physical
Parameter |
Specification |
Dimensions |
150 × 70 × 62.3 mm (5.91 × 2.76 × 2.45 in) |
Fuse Rating |
3.15 A (Schurter PN: 0001.2509) |
Alarm Functions
- Overvoltage Protection:
- Dual, two-fault-tolerant design.
- Restart requires removal of 24 V DC power.
- Undervoltage Detection:
- LED turns ON if output voltage is within acceptable range.
- Relay contact closes at 27.5 V DC (typical).