The Honeywell MP904A & MP904B Pneumatic Damper Operators regulate airflow in heating, cooling, and ventilation systems. These actuators use air pressure for proportional or two-position control, ensuring precise damper blade positioning.
Key Features
- Rolling Diaphragm Operation – Enhances reliability and durability.
- Universal Mounting Bracket – Supports internal installation for Honeywell Moduflow® dampers or external installation on all damper types.
- Optional Positive Positioner – Provides accurate positioning under varying load conditions.
Specifications
Model Variants
- MP904A – Standard operator with positioner.
- MP904B – Standard operator without positioner.
Operating Parameters
Specification | MP904A | MP904B |
---|---|---|
Max. Safe Air Pressure | 25 lb/in² (172 kPa) | 25 lb/in² (172 kPa) |
Start Point Pressure | Adjustable 3-10 lb/in² (20-70 kPa) | Factory set at 2, 3, or 7 lb/in² (15, 20, or 50 kPa) |
Operating Range | See Tables 1 & 2 | See Tables 1 & 2 |
Damper Load Rating | See Tables 1 & 2 | See Tables 1 & 2 |
Force Exerted (Including Tolerances)
Pressure | MP904A | MP904B (2-7 lb/in²) | MP904B (3-13 lb/in²) | MP904B (7-13 lb/in²) |
---|---|---|---|---|
0 lb/in² (0 kPa) | 150 lb (68 kg) | 40 lb (18 kg) | 62 lb (28 kg) | 150 lb (68 kg) |
18 lb/in² (125 kPa) | 90 lb (41 kg), 140 lb (64 kg) | 250 lb (103 kg) | 100 lb (45 kg) | 90 lb (41 kg) |
Stroke & Adjustment
Stroke Type | MP904A & MP904B (3-13 lb/in²) | MP904B (2-7 lb/in²) | MP904B (7-13 lb/in²) |
---|---|---|---|
Factory Set Stroke | 3.5 in. (89 mm) | 3.5 in. (89 mm) (Adjustable: 2-3.5 in.) | 3 in. (76 mm) (Adjustable: 2-3.5 in.) |
Stroke Stop Kits | Available separately | Included | Included |
- Optional Stroke Start Adjustment – Increases stroke start point by up to 1/2 in. (13 mm).
- Stroke Stop Kit – Reduces full stroke travel up to 1.25 in. (32 mm) for 2-7 lb/in² range and 0.75 in. (19 mm) for 7-13 lb/in² range.
Environmental & Material Specifications
Parameter | Value |
---|---|
Ambient Temperature Range | -20 to 160°F (-29 to 71°C) |
Air Connection | 1/8″ NPT female (with factory-installed push-on connector for 5/32″ and 1/4″ OD plastic tubing) |
Finish | Cast aluminum & stainless steel |
Diaphragm | Neoprene, rolling type |
Dimensions (Excluding Bracket) | Length: 8-7/8 in. (225 mm), Diameter: 6-1/4 in. (159 mm) |
Mounting | Bracket & screws provided |
Accessories
- Linkage for External Mounting – Connects 1/2″ (13 mm) OD shaft (Part No. 14002061-001).
- Stroke Start Adjustment Nuts – Two required (Part No. 304662).
- Stroke Stop Adjustment Kit – (Part No. 314959A).
- Crank Arm for 3/8″ (9 mm) Shaft – (Part No. 26025B).
- Crank Arm Ball Joint – (Part No. 315321-00062).
- Additional Accessories – See Form No. 74-5413 for MP909A-D Operator Accessories.
Ordering Information
When ordering, specify:
✔ Model Number
✔ Mounting Type (Internal or External)
✔ Pressure Range
✔ Accessories Needed
Typical Operation
MP904A – Sequential Damper Control
- Used with direct-acting controllers to control damper sections in sequence.
- An increase in temperature at LP914 increases branch line pressure, causing damper M2 to fully actuate before M1 starts moving.
- Provides accurate damper positioning under varying load conditions.
MP904B – Central Fan System Operation
- Works with manual-positioning switch (S1) and electric-pneumatic relay (R1).
- Turning fan ON supplies pressure to the operator, opening the damper to a pre-set position.
- When used with MP904A, ensure MP904B operates at 7-13 lb/in² range for compatibility.
The Honeywell MP904A & MP904B Pneumatic Damper Operators provide precise and reliable airflow control, making them ideal for HVAC, industrial ventilation, and environmental management applications.