Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

Honeywell Other Modules/

Honeywell SC-UCMX01 51307195-175 Non-Redundant Controller

Brand: Honeywell
Model Number: SC-UCMX01
Part Number: 51307195-175
Type: Non-Redundant Controller
Product Origin: United States
Payment: T/T, Western Union, Credit Card
Price: USD 120
Dimensions: 190 mm x 99 mm x 141 mm
Weight: 700 g
Warranty: 12 months

  • Product Details

The ControlEdge RTU features an innovative modular hardware design, allowing processor modules to connect to IOTAs with only passive devices like cable connectors and an expansion I/O connector for seamless I/O expansion.

Non-Redundant Controller Overview

  • Model Number: SC-UCMX01
  • Description: Non-redundant Controller with onboard IOM
  • Rated Input Voltage: 24 VDC ± 25%
  • Input Voltage Range: 18 to 30 VDC
  • Maximum Ripple Voltage: 120 mVpp
  • Maximum Rated Input Current: 1.20 A at 30 VDC (controller plus 9 IOMs)

Hardware Summary

  1. Power Input: 18-30 VDC
  2. RS485 Ports: 2
  3. RS232 Ports: 2
  4. Ethernet Ports: 2
  5. Onboard I/O: 28 (non-redundant RTU only)
  6. SD Card Slot
  7. Status LEDs
  8. Expansion I/O Connector

Performance Specifications

  • Processor: Dual Core ARM® Cortex™-A9, 667 MHz
  • Dynamic Memory (RAM): 128 MB
  • Program Memory (Flash): 32 MB
  • Nonvolatile Memory: 4 Mbits
  • Nonvolatile Memory Data Life: 20+ years (no battery required)
  • Real-Time Clock Resolution: 1 ms
  • Execution Cycle Time: ≥ 50 ms
  • Time Synchronization: SNTP or DNP3
  • Programming Port: Ethernet port
  • SD Card Support: 32GB Class 6/Class 10
  • Datalog Media: Flash memory or optional SD Card
  • Datalog Rate: Configurable (1s, 5s, 10s, 1m, 5m, 10m, 1h)
  • Datalog Timestamp Resolution: 1 ms

Ethernet Specifications

  • Number of Ports: 2 (Non-Redundant Controller)
  • Network Connection: Shielded RJ45, auto-crossover
  • Network Port Speed: 10/100BaseTx, auto-detecting
  • Isolation: 1500 Volts RMS (1 min)
  • Concurrent Connections: 64
  • Protocols Supported: TCP/IP, ARP, UDP, ICMP, DHCP, Modbus TCP, DNP3 TCP, HART-IP

Serial Specifications

  • Number of Ports: 2 x RS232, 2 x RS485
  • Supported Baud Rates: 300 to 115200
  • RS232 Distance: 15m
  • RS485 Distance: 1200m (32 max slaves)
  • Protocols Supported: Modbus RTU, Enron Modbus

DNP3 Protocol Specifications

  • Device Function: Outstation (Slave)
  • Register Capacity: 2000 per Ethernet port
  • Events Buffered: 80,000 (Flash), 200,000 (SD Card)

Modbus Protocol Specifications

  • Device Function: Master and Slave
  • Register Capacity: 8000 registers per port

Watchdog Feature

  • CPU Watchdog: Automatically resets CPU on error detection; status LED flashes error code

Power Consumption (Model: SC-UCMX01)

  • Minimum Power Consumption: 1.7 W (no expansion IOMs)
  • Maximum Power Consumption: 3.4 W (no expansion IOMs)

Dimensions and Weight

  • Dimensions: 190 mm x 99 mm x 141 mm
  • Weight: 700 g

Operating Conditions

  • Mounting: DIN rail (TH35-7.5)
  • Operating Temperature: -40 to 75°C (-40 to 85°C storage)
  • Humidity: 5% to 95% RH (non-condensing)

Standards and Approvals

  • Hazardous Locations Approvals:
    • FM Class I, Division 2
    • CSA Class I, Division 2
    • ATEX II 3 G
    • IECEx Ex nA IIC T4 Gc
  • CE Compliance Standards: LVD, EMC

Other Standards

  • Flammability: UL 94 V-0
  • Vibration: IEC 60068-2-6, 1.0 g (10-150 Hz)

Model Numbers

  • SC-UCMX01: Non-redundant Controller with Onboard Mixed I/O Module (28 channels)

Contact Us

Let us help you find the automation parts you need with reliable quality and dedicated support!

Prev:

Next:

Leave a Reply

Phone +8615915488782

Skype live:.cid.2196513eef2d5350

WhatsApp 8615915488782

WeChat QR Code WeChat

E-Mail uma@meloauto.com

Back to top Back to top

WeChat

WeChat QR Code

Scan the QR Code with WeChat

Leave a message