The MP 3101 S2 is a Trident system component designed for critical safety and control applications. Each Trident system requires a minimum configuration with one MP baseplate housing three main processors (MPs). Each MP module operates as an independent channel within the Trident system and includes dedicated processors for system executive and I/O operations.
Processor and Firmware Components
- System Executive (SX): Manages application control, system diagnostics, TriBus communication, voting, and TriStation/Modbus communication.
- Input/Output Executive (IOX): Manages I/O operations, including ASIC communication, I/O control, and diagnostics.
Main Processor Specifications
- Application Processor:
- Processor: Motorola MPC860, 32-bit, 50 MHz
- Flash PROM: 6 MB (CRC-protected), for SX, IOX, and control application storage
- DRAM: 16 MB, for control application execution, program, and SOE data with byte parity
- NVRAM: 8 KB (CRC-protected) for retentive variables
- Clock Accuracy:
- Power on: 1 sec/day typical, 2.2 sec/day max
- Power off (battery-backed): 2.2 sec/day typical, 9.2 sec/day max
- Battery: ½ AA lithium, 15-year predicted life
- Communication:
- TriBus: 25 Mbps, CRC-protected, 32-bit + parity DMA
- TriStation Port: 10BaseT Ethernet with RJ-45 connector on the baseplate
- Modbus Port: RS-232/485 DTE, DB-9-pin connector on the baseplate
- Debug Port: RJ-12 connector shared between SX and IOX for diagnostics
- Communication Bus: RS-485, 2 Mbps HDLC
- Alarm Contacts: Redundant, normally closed
Input/Output Processor Specifications
- I/O Processor:
- Processor: Motorola MPC860, 32-bit, 50 MHz
- DRAM: 16 MB for IOX execution with byte parity
- Shared Memory: 128 KB for SX-IOX communication with byte parity
- Diagnostic Bus: 2 Mbps HDLC for MP channel I/O diagnostic communication
- I/O Bus: RS-485, 2 Mbps HDLC
- Debug Port: RJ-12 connector on baseplate, shared with SX debug
Power Specifications
- Logic Power:
- Nominal Input Voltage: 24 V DC
- Operational Voltage Range: 24 V DC –15%/+20% + 5% AC ripple (19.2 – 30 V DC)
- Maximum Input Voltage: 33 V DC
- Power Dissipation: 8 W max
- Short Circuit Current Limit: 2.4 A max
- Functional-Earth-to-Logic-Ground Isolation: 0 V
Communication Ports
- Modbus Port:
- Connector: DB-9-pin DTE, shielded
- Max Cable Length: RS-232 (15 m), RS-485 (1.2 km)
- Supported Rates: 1200 to 115.2 Kbps
- Protocols: Slave, RTU mode, optional parity, 1 stop bit
- Isolation: 500 V DC
- Network Port:
- Connector: 10BaseT RJ-45, shielded
- Max Cable Length: 100 m (category 5 twisted-pair)
- Protocol: TriStation, TSAA, Triconex Peer-to-Peer
- Isolation: 500 V DC
- System and IO Executive Debug Ports:
- Connector: RJ-12
- Max Cable Length: 8 m
- Protocol: RS-232, 9600 bps, ASCII
- Isolation: 500 V DC
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat