The Yokogawa NFAI143-S01 is an analog input module designed for applications that require isolated current input channels. This module supports 16 channels of 4-20 mA input signals and offers high accuracy and reliability, making it ideal for industrial environments.
Key Specifications
- Model: NFAI143
- Number of Input Channels: 16 isolated channels
- Input Signal: 4 to 20 mA
- Allowable Input Current: Up to 24 mA
- Withstanding Voltage: 1500 V AC for 1 minute between input and system (may vary with certain cable types)
- Overcurrent Protection: Included
- Input Resistance:
- Power ON: 250 Ω
- Power OFF: 500 kΩ or higher
- Accuracy: ±0.1% of full scale
- Data Refresh Cycle: 10 ms
- Input Step Response Time: 100 ms
- Transmitter Power Supply: 24.0 to 25.5 V (with output current limit of 25 mA)
- Configurable for 2-wire or 4-wire Transmitters: Configurable per channel using a setting pin
- Temperature Drift: Maximum ±0.01% per °C
- Maximum Current Consumption:
- 230 mA at 5 V DC
- 540 mA at 24 V DC
- Weight: 0.3 kg
- External Connection Options: Pressure clamp terminal, MIL connector cable
- HART Communication: Available (optional)
Note:
- 24 V DC must be supplied to the analog field power supply terminal of the power supply module for operation.
- For intrinsically safe applications, an isolation barrier should be used instead of a Zener barrier.
Models and Suffix Codes
- Model: NFAI143 (Analog Input Module for 4-20 mA, 16 channels, isolated)
- Suffix Codes:
- -S: Standard Type
- 0: Basic type
- 1: Includes ISA Standard G3 option for environmental durability