The Ovation 1C31227G01 is an 8 – channel analog input module. It targets industrial applications that need to precisely measure 4 – 20 mA signals. It offers high accuracy, has internal diagnostics, and can self – calibrate, thus ensuring reliable data acquisition.
Key Features
8 Analog Input Channels supporting 4-20 mA signals
14-bit Resolution for high-accuracy measurements
On-Demand Self-Calibration by the Ovation Controller
Internal Diagnostics for module operating faults, out-of-range detection, and open-loop detection
1000V AC/DC Dielectric Isolation (Channel-to-Channel & Channel-to-Logic)
Configurable Normal Mode and Common Mode Rejection for enhanced noise immunity
Specifications
Electrical Specifications
Parameter | Value |
---|---|
Number of Channels | 8 |
Input Range | 4 – 20 mA ±1V |
Resolution | 14 bits (Group 1), 13 bits & Sign (Group 2) |
Guaranteed Accuracy (@25°C) | ±0.10% of full-scale value ±1/2LSB @99.7% confidence |
Temperature Coefficient | ±0.24% of full-scale value (0 to 60°C) |
Input Impedance | 10 MΩ (Voltage Input Only) |
Sampling Rate | 20 times/sec (60 Hz rejection), 25 times/sec (50 Hz rejection) |
Diagnostics | Internal module faults, out-of-range detection, open-loop detection |
Normal Mode Rejection | 60 dB @50/60 Hz ±1/2%, 30 dB (typical) @50/60 Hz ±5% |
Common Mode Rejection | 120 dB @ DC or nominal 50/60 Hz, 100 dB (typical) for line frequency ±5% |
Power & Environmental Specifications
Parameter | Value |
---|---|
Module Power Consumption (Main) | 2.4 W typical, 3.125 W max |
Module Power Consumption (Auxiliary – 1C31227G01) | 3.84 W typical (8 inputs @ 20 mA each) |
Auxiliary Power Supply Voltage | 24 VDC |
Operating Temperature Range | 0 to 60°C (32°F to 140°F) |
Storage Temperature Range | -40°C to 85°C (-40°F to 185°F) |
Humidity (Non-Condensing) | 0 to 95% |
Field Wiring & Connections
The 1C31227G01 Personality Module includes a wiring diagram label for easy field installation. Proper wiring techniques, including shielded twisted pair cables, are recommended for noise reduction.
Terminal Block Abbreviations
Abbreviation | Definition |
---|---|
A1 – A8 (+) | Analog Input Positive Terminal (Connected to Field Device +) |
A1 – A8 (-) | Analog Input Negative Terminal (Voltage Input Group Only) |
P-1 – P-8 | Loop Power Output Terminals (For Locally Powered Loops) |
CI1 – CI8 | Current Input Terminals |
SH1 – SH8 | Shield Terminal Connection |
RSV | Reserved Terminal (No Connections Allowed) |
PS+, PS- | Auxiliary Power Supply Terminals |
WeChat
Scan the QR Code with wechat