The Ovation 5X00119G01 RTD Input Module is designed to convert Resistance Temperature Detector (RTD) inputs into precise digital data. This digital output is transmitted to the Ovation Controller for accurate processing and monitoring.
Module Components and Compatibility
Electronics Module
- The 5X00119G01 Electronics Module handles inputs across various RTD ranges.
- It is compatible solely with the 5X00121G01 Personality Module.
- Not applicable for CE Mark-certified systems.
Personality Module
- The 5X00121G01 Personality Module works exclusively with the 5X00119G01 Electronics Module for RTD input conversion.
Key Features and Design
The 8-channel RTD module consists of:
- Electronics Module:
- Includes a logic printed circuit board (LIA) and a field terminal board (FTD).
- Personality Module:
- Contains a single printed circuit board (PTD).
This modular design allows easy integration and ensures reliable RTD signal conversion.
Specifications
Channel Capacity
- Supports eight RTD inputs.
Sampling Rate
- 50 Hz Mode:
- Processes 16.67 samples per second under normal conditions.
- Drops to 3 samples/second when measuring lead resistance in 3-wire mode.
- 60 Hz Mode:
- Processes 20 samples per second normally.
- Drops to 2 samples/second in 3-wire mode during lead resistance measurement.
- Self-Calibration: Performed on demand, reducing the rate to 1 sample/second.
Resolution and Accuracy
- Resolution: 12-bit precision for detailed data representation.
- Accuracy: ±0.10% at 25°C, with advanced compensation for drift and resistance.
- Temperature Coefficient: 10 ppm/°C ensures high stability.
Isolation
- Channel-to-Channel: 200V AC/DC.
- Channel-to-Logic: 1000V AC/DC.
Power Consumption
- Typical: 3.6 W.
- Maximum: 4.2 W.
Environmental Limits
- Operating Temperature: 0°C to 60°C (32°F to 140°F).
- Storage Temperature: -40°C to 85°C (-40°F to 185°F).
- Humidity: Up to 95% non-condensing.
Diagnostic and Functional Indicators
LED Indicators
- Power OK (Green): Signals stable power supply.
- Communications OK (Green): Indicates active communication with the controller.
- Internal Fault (Red): Lights up for initialization, errors, or uncalibrated states.
- Channel Errors (CH1–CH8 Red): Indicates channel-specific issues, such as overrange or communication failure.
Applications
This module is ideal for systems requiring high-precision temperature measurements from multiple RTDs. Its robust design ensures reliability in industrial environments, with features like high input impedance and advanced calibration capabilities for optimal performance.
Contact Us
- Phone: +86-15915488782
- Email: uma@meloauto.com
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat