The FOXBORO P0917YZ FCP270 Field Control Processor 270 is a distributed, optionally fault-tolerant, field-mounted controller that performs process control and alarming functions according to a user-defined control strategy.
Key Features and Functions:
- Performs regulatory, logic, timing, and sequential control together with connected Fieldbus Modules (FBMs).
- Performs data acquisition and alarm detection and notification.
- Supports up to 32 200 Series FBMs (Compact or standard).
- Supports up to 128 200 Series FBMs with a Fieldbus Expansion Module 100 (FEM100).
- Supports up to 64 of the 100 Series FBMs.
- No Fieldbus Communication Module is required.
- Connects to the MESH control network via standard fiber optic 100 Mbps Ethernet.
- Utilizes a rugged, die-cast aluminum housing for mounting in a non-vented field enclosure.
- Can operate in Class G3 harsh environments.
- Is CE certified for field mounting in enclosures.
- Supports both the 2 Mbps or 268 Kbps HDLC fieldbuses simultaneously, allowing connections to both 200 Series and 100 Series FBMs.
- Offers unique, patented, fault-tolerant operation using two control modules to improve reliability relative to other process controllers.
- Employs versatile control algorithms and a wide variety of FBMs for control capabilities across a broad range of process applications.
Functional Specifications:
- Processor Type: Microprocessor-based AMD Elan 520 (running at 100 MHz) with stored programs and high-speed communication capability. The CommControl™ ASIC with an internal 80186 controls the communication to the I/O Modules (FBMs).
- Memory:
- Size:
- 16 MB SDRAM
- 32 MB flash memory
- Error Detection: ECC providing single-bit error detection and correction as well as multiple-bit error detection.
- Size:
- Process I/O Communications (with FBMs):
- Module Fieldbus Type: HDLC
- Transmission Rate:
- 2 Mbps for 200 Series FBMs
- 268 Kbps for 100 Series FBMs
- Process I/O Capacity:
- 2 Mbps HDLC Fieldbus: Up to 32 maximum without FEM100 modules; with FEM100, supports up to 128 FBMs.
- 268 Kbps HDLC Fieldbus: Up to 64 maximum depending on control processor sizing constraints.
- Mixed Capacity: Total of 64 modules maximum when mixing 100 Series and 200 Series FBMs.
- Memory Allocation for Blocks: 5.8 MB
- Maximum Number of Blocks Configured: 4000 for FCP270 or fault-tolerant FCP270 pair.
- Block Executions Per Second: Maximum of 10,000 blocks/second.
- Maximum Number of IPC Connections: 131 (100 for source points, 30 for sink points, 1 for internal use).
- Power Requirements:
- Input Voltage (Redundant): 24 V DC typical
- Consumption (Per Non-Fault-Tolerant Module): 8.5 W maximum
Regulatory Compliance:
- Electromagnetic Compatibility (EMC): Meets European EMC Directive 89/336/EEC, including various immunity and emission standards.
Environmental Specifications:
- Operating Temperature: 0 to +60°C (+32 to +140°F)
- Relative Humidity: 5 to 95% (Noncondensing)
- Altitude: -300 to +3,000 m (-1,000 to +10,000 ft)
- Contamination: Class G3 (Harsh)
- Vibration: 0.5 g (5 to 500 Hz)
Physical Specifications:
- Configuration: Single processor module; the fault-tolerant version consists of two processor modules.
- Mounting: Can be placed in device-specific 2- or 4-position baseplates designed for horizontal or vertical mounting.
- Dimensions – Module:
- Height: 103 mm (4.04 in) / 114 mm (4.50 in including mounting lugs)
- Width: 51.5 mm (2.03 in)
- Depth: 147 mm (5.80 in)
- Mass (Maximum): 0.6 kg (1.3 lb) for a single, non-fault-tolerant module.
Fiber Optic Cabling:
- Ethernet Switch to FCP270:
- Connectors: One MT-RJ Connector; Two ceramic type LC connectors with clip.
- Cable Material: Multimode fiber (MMF) 62.5/125 µm plenum.
- Maximum Length: 2 km (6,560 ft) from the Ethernet switch to the FCP270.
Contact Us
- Phone: +86-15915488782
- Email: uma@meloauto.com
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat