The Schneider Electric LUCB05BL is an advanced control unit from the TeSys Ultra range, designed for motor control, protection, and diagnostics. It provides overload, short-circuit, and earth fault protection with a manual reset function. The unit operates with three-phase motors and is compatible with multiple power bases and reversing contactor breakers.
Key Features
Motor Protection & Control: Overload, short-circuit, and phase failure protection.
Advanced Diagnostics: Earth fault detection and phase imbalance protection.
Wide Voltage Compatibility: Rated operational voltage of 690V AC at 40-60 Hz.
Adjustable Motor Current Range: 1.25 – 5 A.
Thermal Overload Protection: Class 10 per IEC 60947-6-2 and UL 508 standards.
Plug-in Design: Quick and easy installation with front-face connectivity.
Global Certifications: CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine certified.
Robust Environmental Resistance: Operates at temperatures -25°C to 70°C with high shock and vibration resistance.
Technical Specifications
General Information
Description | Value |
---|---|
Range | TeSys Ultra |
Product Name | TeSys Ultra |
Device Short Name | LUCB05BL |
Product Type | Advanced Control Unit |
Application | Motor Control & Protection |
Utilization Category | AC-41, AC-43, AC-44 |
Motor Power | 1.5 kW (400-440V AC), 2.2 kW (500V AC), 3 kW (690V AC) |
Rated Operational Voltage [Ue] | 690V AC |
Control Circuit Voltage [Uc] | 24V DC |
Control Voltage Limits | 20-27V DC (operation), 14.5V DC (drop-out) |
Motor Current Adjustment Range | 1.25 – 5 A |
Protection & Safety
Protection Type | Availability |
---|---|
Overload Protection | ✔ |
Short-Circuit Protection | ✔ |
Earth Fault Protection | ✔ |
Phase Failure & Imbalance Detection | ✔ |
Thermal Overload Class | Class 10 (40-60 Hz, IEC 60947-6-2, UL 508) |
Impulse Withstand Voltage [Uimp] | 6 kV |
Insulation Voltage [Ui] | 690V (IEC 60947-6-2), 600V (UL 60947-4-1) |
IP Rating | IP20 (front panel & wired terminals), IP40 (outside connection zone) |
Compatibility & Connections
Compatible Power Bases | Compatible Reversing Contactors |
---|---|
LUB12, LUB32, LUB38 | LU2B12BL, LU2B32BL, LU2B38BL |
LUB120, LUB320, LUB380 | – |
Electrical Performance
Description | Value |
---|---|
Typical Current Consumption | 130 mA (LUB12), 220 mA (LUB32/LUB38) |
Heat Dissipation | 2W (LUB12), 3W (LUB32/LUB38) |
Operating Time | 35ms (Opening), 70ms (Closing) |
Environmental Conditions
Condition | Value |
---|---|
Operating Temperature | -25°C to 70°C (-13°F to 158°F) |
Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
Operating Altitude | Up to 2000m (6561 ft) |
Humidity | 0-95% (Non-Condensing) |
Fire Resistance | IEC 60695-2-12 (1760°F / 960°C) |
Mechanical & Installation
Fixing Mode | Plug-in (Front Face) |
---|---|
Dimensions | 45mm (W) × 66mm (H) × 60mm (D) |
Certifications & Compliance
Standards: IEC 60947-6-2, UL 60947-4-1, CSA C22.2 No. 60947-4-1
Certifications: CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine
Ordering & Packaging Information
GTIN | 3389110364088 |
---|---|
Returnability | Yes |
Country of Origin | France |
Package 1 (Single Unit)
Height | Width | Length | Weight |
---|---|---|---|
5 cm (1.97 in) | 8 cm (3.15 in) | 9 cm (3.54 in) | 113 g (3.99 oz) |
Package 2 (23 Units)
Height | Width | Length | Weight |
---|---|---|---|
15 cm (5.91 in) | 30 cm (11.81 in) | 40 cm (15.75 in) | 2.89 kg (6.36 lb) |
WeChat