Overview
The Triconex 3625A is a 32-point TMR Supervised or Non-Supervised Digital Output Module, designed for critical control applications. These modules work with 16-point commoned field termination panels and are suitable for energize-to-trip and de-energize-to-trip applications. You can only install the 3625A module in Tricon v10.2 and later systems.
The 3625A module separates the field power supply into groups of 16 points, maintaining a common return. This modification doesn’t affect its compatibility with all applications that use the 3625 module.
Power Requirements
Invensys recommends wiring the termination panels in parallel and powering them from a single, redundant field power source. Although you can power the module from four independent field power sources, all sources must maintain a voltage within 5% of the highest voltage supplied. Failing to follow this guideline may cause the module to operate with voter faults and trigger alarms.
3625A Digital Output Specifications
Feature | Specification |
---|---|
Color Code | Dark blue |
Number of Output Signals | 32, commoned |
Recommended Voltage Range | 16-32 VDC |
Nominal Voltage | 24 VDC |
Maximum Voltage | 36 VDC |
Logic Power | < 13 watts |
Current Ratings (Maximum) | 1.70 ±10% amps/point, 5 amps surge/7 ms |
Total Module Output Current | 10 amps/termination panel |
Minimum Required Load | 10 mA |
Maximum Output Leakage | 2.0 mA @ 24 VDC, 2.5 mA @ 32 VDC |
Fuses (Field Termination Module) | Not required; output switches self-protected |
Status Indicator: On or Off State | 1 per point |
Status Indicator: Module Status | Pass, Fault, Load, Active |
Status Indicator: Field Alarm | Load (1 per point) |
System-to-Field Isolation | 1,500 VDC minimum |
Point Supervision | Programmable per point |
Short/Open Circuit Detection | Programmable per supervised point |
Output Diagnostic Fault Coverage | See detailed coverage |
Maximum Output Toggle Rate | Every 60 ms |
Diagnostic Glitch Duration | 2 ms maximum, 200 µs typical |
On-State Voltage Drop | < 0.16 VDC typical @ 250mA; < 1.12 VDC typical @ 1.7A |
With External Termination (10-foot Cable) | < 1.15 VDC typical @ 250mA; < 3.33 VDC typical @ 1.7A |
With External Termination (99-foot Cable) | < 2.71 VDC typical @ 250mA; < 8.92 VDC typical @ 1.7A |
Inductive Kick-Back Protection | Output switches self-protected |
Notes:
- Field Power Configuration: For the 3625A module, group the field power into sets of 16 points with separate termination panels. Make sure to power all points, including unused ones on non-commoned panels.
- Output Toggle Rate: The maximum output toggle rate is 60 ms. This rate ensures proper I/O diagnostics and helps detect faults effectively.
- Installation: The 3625A module works with low-density systems upgraded to v10.2.x or later. For more details, consult “Appendix I, Low-Density Chassis I/O Module Compatibility” in the Field Terminations Guide for Tricon v9–v11 Systems.