Overview
The Triconex 3625A is a 32-point TMR Supervised or Non-Supervised Digital Output Module, designed for critical control applications. These modules work with 16-point commoned field termination panels and are suitable for energize-to-trip and de-energize-to-trip applications. You can only install the 3625A module in Tricon v10.2 and later systems.
The 3625A module separates the field power supply into groups of 16 points, maintaining a common return. This modification doesn’t affect its compatibility with all applications that use the 3625 module.
Power Requirements
Invensys recommends wiring the termination panels in parallel and powering them from a single, redundant field power source. Although you can power the module from four independent field power sources, all sources must maintain a voltage within 5% of the highest voltage supplied. Failing to follow this guideline may cause the module to operate with voter faults and trigger alarms.
3625A Digital Output Specifications
Feature | Specification |
---|---|
Color Code | Dark blue |
Number of Output Signals | 32, commoned |
Recommended Voltage Range | 16-32 VDC |
Nominal Voltage | 24 VDC |
Maximum Voltage | 36 VDC |
Logic Power | < 13 watts |
Current Ratings (Maximum) | 1.70 ±10% amps/point, 5 amps surge/7 ms |
Total Module Output Current | 10 amps/termination panel |
Minimum Required Load | 10 mA |
Maximum Output Leakage | 2.0 mA @ 24 VDC, 2.5 mA @ 32 VDC |
Fuses (Field Termination Module) | Not required; output switches self-protected |
Status Indicator: On or Off State | 1 per point |
Status Indicator: Module Status | Pass, Fault, Load, Active |
Status Indicator: Field Alarm | Load (1 per point) |
System-to-Field Isolation | 1,500 VDC minimum |
Point Supervision | Programmable per point |
Short/Open Circuit Detection | Programmable per supervised point |
Output Diagnostic Fault Coverage | See detailed coverage |
Maximum Output Toggle Rate | Every 60 ms |
Diagnostic Glitch Duration | 2 ms maximum, 200 µs typical |
On-State Voltage Drop | < 0.16 VDC typical @ 250mA; < 1.12 VDC typical @ 1.7A |
With External Termination (10-foot Cable) | < 1.15 VDC typical @ 250mA; < 3.33 VDC typical @ 1.7A |
With External Termination (99-foot Cable) | < 2.71 VDC typical @ 250mA; < 8.92 VDC typical @ 1.7A |
Inductive Kick-Back Protection | Output switches self-protected |
Notes:
- Field Power Configuration: For the 3625A module, group the field power into sets of 16 points with separate termination panels. Make sure to power all points, including unused ones on non-commoned panels.
- Output Toggle Rate: The maximum output toggle rate is 60 ms. This rate ensures proper I/O diagnostics and helps detect faults effectively.
- Installation: The 3625A module works with low-density systems upgraded to v10.2.x or later. For more details, consult “Appendix I, Low-Density Chassis I/O Module Compatibility” in the Field Terminations Guide for Tricon v9–v11 Systems.
About Us
Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.Contact Us
- Phone: +86-15915488782
- Email: [email protected]
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat