Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

Triconex Power Modules/

Triconex DO3401 | Model 3401 Digital Output Module

Brand: Triconex
Product Family: Trident Version 1.2
Model Number: DO3401
Type: Digital Output Module
Product Origin: United States
Payment: T/T, Western Union, Credit Card
Price: USD 120
Dimensions: 4.5cm*18.8cm*20.8cm
Weight: 1.4kg
Warranty: 12 months

  • Product Details
  • Technical Documentation

The Model 3401 Digital Output Module is designed for safe, reliable, and highly available operation in critical systems. It employs advanced diagnostics, redundant circuitry, and hot-sparing capabilities to ensure performance and fault detection.


Available Components

Model Description Voltage Type
3401 Digital Output Module 24 V DC Commoned
2401 Digital Output Baseplate Direct Termination
2402 Digital Output Baseplate Current Limited

Features

  1. Redundant Circuitry:
    • Triple Modular Redundancy (TMR) with ASIC-based quad output voting.
    • Ensures high availability by voting on signals before applying them to the load.
  2. Output Voter Diagnostic (OVD):
    • Detects stuck-on or stuck-off points and switches within 500 ms.
    • Enables transparent loop-back testing without affecting most field devices.
    • Configurable to disable OVD for sensitive devices.
  3. Hot-Sparing:
    • Supports online replacement of faulty modules.
  4. Mechanical Keying:
    • Prevents improper installation in the configured baseplate.

Model 3401 Specifications

Feature Specification
Points 16, commoned
Nominal Output Voltage 24 V DC
Operational Voltage Range 15–30 V DC
Max. Output Voltage 33 V DC
Reverse Input Voltage –0.6 V DC
Output Current – Switching: <4.8 A (self-limiting), 3 A typical
– Carry: >0.7 A (self-limiting), 1.5 A typical
Field Alarms Loss of field power, output point shorted (On/Off)
Loop-back Thresholds – Off: 0–5 V DC
– Transition: 6–14 V DC
– On: 15–30 V DC
Leakage to Load (Off-state) <1 mA
Diagnostic Glitch Duration Max: <2 ms; Typical: 500 µs
Toggle Rates – Maximum: >20 ms
– Minimum: Not applicable
On-state Voltage Drop <1 V DC @ 1.5 A
Loop-back Scan Time <1 ms for all 16 points
Isolation – Functional to protective earth: 500 V DC, minimum
– Functional to functional-earth (logic): 800 V DC, minimum

 


Contact Us

Let us help you find the automation parts you need with reliable quality and dedicated support!