The TZIDC-200 features a compact design and modular construction, offering an excellent cost-performance ratio. Its fully automatic determination of control parameters allows for optimal adaptation to final control elements, leading to significant time savings and improved control behavior.
General Specifications
- Approvals: Worldwide approvals for Explosion Proof and Intrinsic Safety
- Vibration Immunity: Up to 10 g
- Autostroke Function: Fully automatic adaptation to valves
- Communication Protocols:
- HART protocol standard for full access to smart functions, diagnostics, maintenance, and fault detection
- Designed for fieldbus communication
- Compatibility: One positioner for both linear and rotary actuators
Technical Specifications
- Actuator Travel:
- Rotation Angle: Measured range of 270° / 360°*
- Operating Range for Linear Actuators: Min. 25°, Max. 45°
- Operating Range for Rotary Actuators:
- Min. 25°, Max. <270°
- Min. 25°, Max. 350°* (see Figures 10 & 11)
- Travel Limits: Freely configurable limits from 0% to 100% of total travel (min. range > 20%)
- Travel Time Prolongation: Setting range of 0 to 200 seconds for each direction
- Dead Band Time Limit: Setting range of 0 to 200 seconds
*From HW rev.: 5.01 with order option “S1 – Contactless sensor”
Pneumatic Connections
- Cable Connections:
- Thread ½-14 NPT
- Thread M20 × 1.5
- Air Pipe Connections:
- Thread ¼-18 NPT
- Thread G ¼
- Thread G ½
- Optional: Cable glands and blind plugs as necessary
Compressed Air Output
- Standard Design Range: 0 to 6 bar (0 to 90 psi)
- Marine Version Range: 0 to 5.5 bar (0 to 80 psi)
- Air Capacity:
5 kg/h = 3.9 Nm³/h = 2.3 scfm at 1.4 bar (20 psi) supply air pressure
13 kg/h = 10 Nm³/h = 6 scfm at 6 bar (90 psi) supply air pressure
- Output Function: For single acting or double acting actuators; air vents from actuator or actuator is blocked in case of power failure
- Shut-off Values:
- End position 0% = 0 to 45%
- End position 100% = 55 to 100%
Instrument Air Quality
- Purity Requirements:
- Maximum particle size: 5 μm
- Maximum particle density: 5 mg/m³
- Oil Content: Maximum concentration of 1 mg/m³
- Pressure Dew Point: 10 K below operating temperature
- Supply Pressure:
- Standard design: 1.4 to 6 bar (20 to 90 psi)
- Marine version: 1.6 to 5.5 bar (23 to 80 psi)
- Air Consumption: < 0.03 kg/h / 0.015 scfm
Free of oil, water, and dust in accordance with DIN / ISO 8573-1. Pollution and oil content in accordance with Class 3.
Ordering Information
- Model: TZIDC-200 digital positioner with flameproof enclosure, intelligent, software-configurable with Local Communication Interface (LCI) and HART communication.
- Base Model: V18348-XX- X- X-X-X-X-X-X-X-X (10161310110)
Physical Characteristics
- Case / Mounting: Aluminum case, varnished, suitable for mounting to linear actuators per DIN/IEC 534 / NAMUR or to rotary actuators per VDI/VDE 3845.
- Operation: Integrated operator panel and display in the enclosure cover
- Explosion Protection: IECEx Ex d II C T4/T5/T6 Gb
Additional Options
- Output / Safe Position (Power Failure): Single acting, fail safe
- Connections:
- Cable: Thread ½-14 NPT
- Air Pipe: Thread ¼-18 NPT
- Feedback Modules:
- Plug-in module for analog position feedback, signal range 4 to 20 mA (two-wire)
- Optional Mechanical Kit for Digital Position Feedback: Not included
- Parameter Setting: Factory setting for HART devices
WeChat
Scan the QR Code with wechat