Over 50,000 Brand New, 100% Genuine PLC/PAC & DCS Products!

Yokogawa I/O Modules/

Yokogawa NFAI135-S51 Analog Input Module

Brand: Yokogawa
Product Family: FCN Autonomous Controller
Model Number: NFAI135-S51
Type: Analog Input Module
Product Origin: Japan
Payment: T/T, Western Union, Credit Card
Price: USD 120
Dimensions: 3.2 cm x 12.7 cm x 12.7 cm
Weight: 0.3 kg
Warranty: 12 months

  • Product Details

The Yokogawa NFAI135-S51 is an advanced Analog Input Module, engineered to handle 4 to 20 mA signals with isolated channels. This module ensures precise, reliable input/output performance, making it ideal for a range of industrial automation applications. Furthermore, its isolated channels safeguard system integrity by preventing interference between signals.

Key Features:

  • Model: NFAI135
  • Number of Channels: 8 input channels, all isolated
  • Input Signal: 4 to 20 mA (current input)
  • Allowable Input Current: Up to 25 mA
  • Accuracy: ±0.1% of full scale
  • Data Refresh Cycle: 10 ms
  • Step Response Time:
    • Input: 100 ms
    • Output: Not applicable
  • Withstanding Voltage:
    • Between input/output and system: 500 V AC for 1 minute
    • Between channels: 500 V AC for 1 minute
  • Power Supply: 20.2 to 29.3 V DC for the transmitter
  • Temperature Drift: Max. ±0.01%/°C
  • Maximum Current Consumption:
    • 360 mA (5 V DC)
    • 450 mA (24 V DC)
  • HART Communication: Available for advanced configuration and diagnostics

Additional Features:

  • Overcurrent Protection: The module incorporates a built-in overcurrent protection circuit to prevent damage.
  • Input Resistance:
    • Power ON: 250 Ω
    • Power OFF: ≥500 kΩ
  • External Connections: Connect using pressure clamp terminals or MIL connector cables.
  • Weight: 0.3 kg
  • Fallback Function:
    • HOLD: Maintains output when fallback is detected.
    • SETV: Outputs a specified value when fallback is detected.
    • Fallback detection time: 4 seconds
  • Usage Notes:
    • HART Communication: Supports bidirectional communication with field devices for easy configuration and troubleshooting. See the GS 34P02Q53-01E manual for detailed HART specifications.
    • Power Supply: A 24 V DC analog field power supply is required for proper module operation.
    • Zener Barriers: Do not use Zener barriers. Use an isolation barrier for intrinsically safe applications to avoid electrical hazards.

Models and Suffix Codes

  • Model: NFAI135 (Analog Input Module, 8 channels, isolated)
  • Suffix Codes:
    • -S: Standard type
    • 5: No explosion protection
    • 1: With ISA Standard G3 option

Contact Us

Let us help you find the automation parts you need with reliable quality and dedicated support!

Prev:

Next:

Leave a Reply

Phone +8615915488782

Skype live:.cid.2196513eef2d5350

WhatsApp 8615915488782

WeChat QR Code WeChat

E-Mail [email protected]

Back to top Back to top

WeChat

WeChat QR Code

Scan the QR Code with WeChat

Leave a message