The Honeywell 10216/2/1 module is a fail-safe digital output module with four 24 Vdc loop-monitored output channels, each capable of driving loads up to 24 W. The module’s total maximum load is 3.6 A. It is designed for both resistive and inductive loads, featuring a built-in suppression diode for inductive load protection.

Key features include:

  • Integrated loop monitoring for lead breakage and short circuit detection.
  • Tested for fail-safe applications, including suppression diode functionality, crosstalk, and de-energization capabilities.
  • Equipped with secondary means of de-energization via the watchdog or processor.

The module requires an I/O backplane for operation, as the outputs need to work with a 10216/A/. range-setting module.


Technical Specifications

General

  • Type Number: 10216/2/1 12401
  • Approvals: CE, TÜV, UL
  • Software Versions: ≥ 3.00
  • Space Requirements: 4 TE, 3 HE (= 4 HP, 3U)

Power

  • 5 Vdc: 15 mA
  • 24 Vdc Internal: 50 mA
  • 24 Vdc External: 15 mA (without output load)

Output

  • Number of Channels: 4
  • Output Specification: 24 Vdc solid-state source, short-circuit proof
  • Maximum Channel Current: 1 A
  • Maximum Total Module Load: 3.6 A (module dissipation limit)
  • Maximum Load Inductance: 0.5 H
  • Maximum Load Capacity: 1 µF
  • Voltage Drop: < 1.3 V at 1 A
  • Off Current: < 0.1 mA
  • Current Sense Voltage Drop: < 1 V at 1 A

Diagnostics and Monitoring

  • Lead Breakage Detection: Monitors for broken leads in the external wiring.
  • Short Circuit Detection: Ensures load safety and integrity.

Key Coding

  • Module Code: Holes A13, C9
  • Rack Code: Large Pins A13, C9

LED Indicators

Each channel is equipped with an LED indicator:

  • Off State: Periodic brief flashes indicate lead breakage tests.
  • On State (Non-redundant): LED remains on with brief, almost invisible flashes for self-tests.
  • On State (Redundant): LEDs alternate flashing between modules in CP1 and CP2 during redundancy checks.

Loop Monitoring Current Settings

Load (W) Current Range (mA) Required Range-setting Module
Spare Channel 4 – 16 None
0.1 – 0.39 W 17 – 47 10216/A/2
0.4 – 1.1 W 48 – 199 10216/A/3
≥ 4.8 W ≥ 200 10216/A/4

Notes

Modules with suffix code 12401 include minor layout modifications to enhance production yield and reliability without functional changes.

For additional details, refer to the FSC Output Modules Data Sheet.(Download PDF File Fail Safe Control Hardware Manual


About Us

  Meloauto – Your Trusted Supplier for Original, Brand-New PLC and DCS Parts Meloauto offer a vast selection of products from globally recognized brands, including Allen Bradley, Bently Nevada, Honeywell, ABB, GE Fanuc, Siemens, Invensys Triconex, ICS Triplex, Foxboro, Yokogawa, Schneider, and Hima, among others. With tens of thousands of new parts ready to ship, Meloauto has successfully served customers across over 50 countries worldwide. We focus on supplying discontinued and hard-to-find items, ensuring each product is in brand-new, original condition.

Contact Us

Let us help you find the automation parts you need with reliable quality and dedicated support!

Prev:

Next:

Leave a Reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Phone +8615915488782

Skype +8615915488782

WhatsApp 8615915488782

WeChat QR Code WeChat

E-Mail [email protected]

Back to top Back to top

WeChat

WeChat QR Code

Scan the QR Code with WeChat

Leave a message