The Honeywell CC-PUIO31 Universal Process I/O Module is a versatile and robust module that supports various field device types with notable flexibility and advanced features. Here’s an analysis of its key features and specifications:
Key Functions
- Multi-functionality:
- Each channel can be configured as:
- Analog Input (AI)
- Analog Output (AO)
- Digital Input (DI)
- Digital Output (DO)
- Pulse Input (PI)
- Supports Sequence of Events (SOE) logging with 1ms resolution.
- Each channel can be configured as:
- Protection and Diagnostics:
- Open Wire Detection (OWD)
- Electronic short circuit protection.
- Safe-state (FAILOPT) behavior configuration for outputs.
- HART Communication:
- HART 7 support for both AI and AO.
- Dedicated HART modem per channel for faster performance.
- High Environmental Tolerance:
- Extended operating temperature range: -40°C to +70°C.
Specifications by Function
Analog Input (AI)
- Channels: Up to 32.
- Input Range: 0-20 mA or 4-20 mA.
- Impedance: 250 Ω.
- Accuracy:
- 0.1% FS at 23.5°C.
- 0.25% FS at -40°C to +70°C.
- Scan Rate: 10 ms.
- Features:
- Open Wire Detection.
- Short circuit current limit: 25 mA.
Analog Output (AO)
- Channels: Up to 32.
- Output Range: 4-20 mA.
- Accuracy:
- 0.35% FS at 25°C.
- Includes linearity.
- Resolution: 12-bit.
- Response Time:
- 80 ms in HART mode.
- 0.25 ms in non-HART mode.
- Load: Maximum 825 Ω at 20 mA.
Digital Input (DI)
- Channels: Up to 32.
- Resolution: 1ms (SOE).
- Open/Closed Detection:
- Open: < 2.0 mA.
- Closed: > 3.2 mA.
- Open Wire Detection: Current thresholds configurable.
Digital Output (DO)
- Channels: Up to 32.
- Type: Solid-state source, short circuit protected.
- Load Current:
- On: 1 mA to 0.5 A (per channel).
- Off: < 0.1 mA.
- Voltage: 24 V typical when on.
Pulse Input (PI)
- Channels: Any 4 channels.
- Frequency: 0-15 kHz.
- Minimum Pulse Width: 25 µs.
- Duty Cycle: Configurable.
Unique Features
- HART Support: Enhances diagnostics and communication for AI and AO channels.
- Energy Limitation: Certified for Zone 2/Division 2 hazardous locations.
- Short Circuit Protection:
- Limits current rapidly to protect the module.
- No effect on other channels during short conditions.
- Failover Behavior:
- Configurable safe-state behavior for both AI and AO.
Models and Redundancy
- Non-Redundant: CC-TUIO31 (9” IOTA).
- Redundant: CC-TUIO41 (12” IOTA).
Contact Us
- Phone: +86-15915488782
- Email: uma@meloauto.com
- WhatsApp: +8615915488782
- Business Hours: 24/7 service
- Address: Unit 601, Powerlong International Center, No. 1599 Luling Road, Siming District, Xiamen City, Fujian, China
WeChat
Scan the QR Code with wechat