Description
The RET615 is a high-performance relay designed for transformer protection and control in utility and industrial power distribution systems. It is part of ABB’s Relion® product family and the 615 series, offering a compact design and withdrawable-unit functionality. This device is optimized for two-winding transformers, unit transformers, step-up transformers, and generator-transformer blocks.
The RET615 is engineered to maximize the benefits of the IEC 61850 standard, ensuring interoperability between substation automation devices. Once the user applies the required application-specific settings, the relay is ready for immediate operation.
Key Features
- Comprehensive Protection:
- Transformer differential protection (87T) with harmonic restraint.
- Restricted ground-fault protection for high-speed fault clearance.
- Thermal overload, short circuit, and overcurrent protection.
- Directional and non-directional ground fault and overvoltage protection.
- Circuit breaker failure and arc flash detection (optional).
- Advanced Monitoring:
- Continuous measurement of high voltage (HV) and low voltage (LV) currents.
- Symmetrical components, active/reactive power, and energy monitoring.
- Supports up to eight RTD inputs for thermal management.
- Disturbance Recorder:
- Records up to 12 analog and 64 binary signals.
- Stores data in non-volatile memory for post-event analysis.
- Communication and Control:
- Full IEC 61850 Edition 2 support, including GOOSE messaging and sampled values.
- Additional protocols: Modbus® (RTU, ASCII, TCP) and DNP3 (serial/TCP).
- Optional redundant Ethernet communication for enhanced reliability.
Technical Specifications
- Physical Dimensions:
- Width: Frame 177 mm, Case 164 mm.
- Height: Frame 177 mm, Case 160 mm.
- Depth: 201 mm.
- Weight: Complete unit 4.1 kg, Plug-in unit only 2.1 kg.
- Inputs and Outputs:
- Six phase-current inputs, one neutral-current input.
- Three phase-voltage inputs and one residual voltage input.
- Optional RTD inputs for temperature and pressure measurements.
- Power Supply:
- Nominal auxiliary voltage: 24–250 V DC or 100–240 V AC.
- Maximum interruption time: 50 ms without resetting.
- Operating Conditions:
- Operating temperature: -25°C to +55°C (short-term: -40°C to +85°C).
- Humidity: <93% (non-condensing).
- Altitude: Up to 2000 m.
- Standards and Certifications:
- EMC compliance: IEC 60255-26, EN 55011.
- Environmental protection: IP54 front side, IP20 rear side.
Applications
- Protection of two-winding transformers in power distribution systems.
- Step-up transformers in generator-transformer blocks.
- Supervision and control of circuit breakers, disconnectors, and grounding switches.
- Monitoring of transformer thermal and operational conditions to ensure reliability.
For detailed information, please refer to the ABB RET615 User Manual